Owner manual

Appendix A
Specifications
A-1
Table A.1 Specifications
ELECTRICAL – CONTROL CIRCUIT
Power Supply Input
Voltage Rating 110/240 VAC, 50/60 Hz
Operating Range 85 to 264 VAC, 47–63 Hz
Maximum Power Consumption 6 watts
Maximum Power Interruption Time 20 ms.
Trip Relay Output
For all except
193- or 592-CIL_
or CIM_
For 193- or
592-CIL_ or CIM_
Type Hard Contact
Rated Operational Voltage 240 VAC
Contact Rating Designation B300 A300
Maximum Operating Current 5 mA 10 mA
Minimum Operating Current 10 mA 100 mA
Minimum Leakage Current 10 mA 10 mA
Resistive Load Rating (pF = 1.0)
5A, 250 VAC
5A, 30 VDC
10A, 250 VAC
10A, 30 VDC
Inductive Load Rating (pF = 0.4)
(L/R = 7ms)
2A, 250 VAC
2A, 30 VDC
3A, 250 VAC
3A, 30 VDC
Recommended Control Circuit Fuse
6A Form 101
Semi-conductor
Fuse
(Gould P/N
A60 Q6-2)
12A Form 101
Semi-conductor
Fuse
(Gould P/N
A60 Q12-2)
Rated Number of Operations 10,000
OUT A and OUT B Outputs
For all except
193- or 592-CIL_
or CIM_
For 193- or
592-CIL_ or CIM_
Type Triac
Rated Insulation Voltage 250 VAC
Operating Range 85 to 264 VAC, 47–63 Hz
Switching Element Rating
Designation
SE SD
Utilization Category AC15 AC15
Rated Operational Current 0.5A 1.0A
Minimum Operational Current 20 mA 50 mA
Maximum Off-state Current 10 mA 10 mA
Maximum Voltage Drop 3.5V 3.5V
Replaceable Fuse
(Ceramic 5 20mm, 250 VAC
2.0A 5.0A
Recommended Control Circuit Fuse
1A Class CC
(ATQR-1)
5A Form 101 Semi-
conductor Fuse
(Gould P/N
A60 Q5-2)
Maximum Bul. 500 Contactor Coil
Size 2
110–240 VAC
Size 4
110–240 VAC
Maximum Bul. 100 Contactor Coil
A75
110–240 VAC
B180
110–240 VAC
Rated Number of Operations 10,000,000
Leakage current is due to noise suppression circuitry.