Owner's manual

7-2 Troubleshooting
1901-UM020C-EN-P June 2013
Table 7.B Troubleshooting Guide
Problem orTrip
indicated
Indication of the following conditions Possible Solutions
Pullout trip (power factor)
[POWER FACTOR TRIP]
Motor overloaded
Loss of DC excitation
Static exciter DC current level set too low
Lessen the motor loading and/or overload
Repair static exciter
Increase current setting on static exciter
Squirrel-cage Protection
Trip
[SQ. CAGE PROT’N]
Motor overloaded at start Remove or lessen load for start
Incomplete Start Sequence
Time Exceeded
[INCOMPLETE START]
Motor overloaded at start
Field contactor or FC pilot relay coil failure
Remove or lessen load for start
Replace coil(s)
No Transducer Input
[PF–NO XDCR INPUT]
The transducer is putting out less than 12 mA
when the motor is off (should be 12 mA)
Check the wiring for the voltage sensing on the
transducer board.
Replace phase angle transducer board if necessary.
Replace analog card in SyncPro rack
CT Open/Shorted
[PF–CT OPEN/SHORT]
The CT is either open or shorted. Check the wiring between the CT and the
transducer board.
Replace the CT if necessary.
CT Reversed
[PF–CT REVERSED]
The CT is incorrectly wired to the transducer
board.
Reverse the leads of the CT at the transducer
board.
No Signal @ SLC
[PF–NO SIGNAL@SyncPro]
There is no signal at the SLC analog card from
the PF transducer board.
Check the wiring between the transducer board
and the SLC analog card.
Ensure that there is power to the transducer board.
Replace the SLC analog card or transducer
board as required.
Transducer Problem
[PF–XDCR PROBLEM]
The transducer is behaving unpredictably. This is an all-encompassing fault and could
include anything from the CT, the transducer board,
or the SLC analog card.
PulseBoard24VFailure
[PULSE BOARD 24 V]
Connection has not been made between the
analog/digital pulse board and the SyncPro DC
input card or from the discharge resistor to the
same A/D pulse board.
1746-P2 power supply has had a failure of the 24
V supply.
Check the connections at the A/D pulse board.
Check fuse in power supply. Check for 24 V at
power supply. Replace power supply if necessary.
Replace A/D pulse board.
Field Voltage Loss
[FIELD VOLT LOSS]
The static exciter is not actively producing DC or
the FVR relay coil has failed.
Wrong polarity on FVR coil.
Incorrect voltage rating of FVR coil.
Exciter Enable (EE) relay did not pick up.
Service the static exciter or repair the FVR relay.
Check polarity on FVR coil.
Check voltage rating of FVR coil.
Verify the control circuit.
Field Current Loss
[FIELD AMPS LOSS]
The current relay which monitors the motor field
current is not providing an energized contact to
verify that the static is functional.
Check both the field current relay and the static
exciter for possible failures.
No Field Coil Feedback
[FIELD CONTACTOR]
The SyncPro has requested the field contactor to
energize but the feedback contact from this
contactor is not showing as closed.
The field contactor coil has failed. Replace the coil.
The connection to the FC auxiliary has not been
made. Check the wiring.
The FC auxiliary contact has failed. Replace the
contact.
Reversed PF @ SyncPro
[REVERSED PF@SLC]
The connections from the PF transducer to the
analog card have been accidentally reversed.
Switch the positive and negative transducer
output leads at the analog card.
External Hardware Fault
[EXTERNAL TRIP]
An external device to the SyncPro is not
functioning as expected.
Check external devices.