Owner's manual
1-12 Product Description
1901-UM020C-EN-P – June 2013
Specifications (cont.) Specific Specifications (for Phase Angle Transducer)
General
Accuracy: 3% span
Housing: Flame retardant plastic case
Weight: 2.4 kg maximum
Climate
Storage: -20 to 70
°C (-4 to 158°F)
Temp. range: -20 to 70
°C (-4 to 158°F) storage
Operational @ 0 to 60
°C (32 to 140°F)
Calibrated @ 23
°C (73°F)
Humidity: Up to 95% RH. Non-condensing
Input
Frequency: 50 or 60 Hz
Current: Any value between 0.2 and 10 A
Range (A): 20 - 120%
Burden: 5 VA Maximum
Voltage: Between 115V/230V ±10%
Range (V): ± 20 % (20 - 120% with sep. aux.)
Burden 1 VA maximum
Overload Capacity
Six times rated current for 30 seconds
1.25 rated voltage for 10 seconds
Electrical Tests
Dielectric Test: 2kV RMS to BS 5458
Impulse Test: 5kV transient as BEAMA 219 & BS923
Surge Withstand: ANSI C37-90A
Certification: CSA Approved
DTAM Specifications
Refer to Publication 1747-NC013, Appendix A-1, A-2.
SLC500 Specifications
Refer to Publication 1747-NI002, SHT 1-4
Power Supply Specifications
Refer to Publication 1747-NI002, SHT 1-7