Manual

6 FlexArmor PROFIBUS Adapter Module
Publication 1798-IN011A-EN-P - March 2002
Troubleshooting with the Indicators
Diagnostic indicators are located on the front of the adapter module.
They show both normal operation and error conditions in your
PROFIBUS I/O system. The indicators are:
STATUS
PROFIBUS
The following table describes status indicators.
The following table describes PROFIBUS status indicators.
Specifications
STATUS Indicator
Indicator Status
OFF No power
Solid Green Normal operation
Flashing Red/OFF Recoverable fault
- FlexArmor I/O module bad
- Incorrect FlexArmor I/O module installed
- Node address changed since power up
Solid Red Unrecoverable fault
PROFIBUS Indicator
Indicator Status
OFF No power or no communication
Solid Green Data is being transmitted and received
Flashing Red/OFF Recoverable fault
- Invalid Send Parameter data
- Invalid Check Configuration data
Solid Red Unrecoverable fault
- Unable to communicate
FlexArmor PROFIBUS Adapter Specifications
Network Protocol PROFIBUS-DP (EN50170)
Communication of the slave with a Class 1 master
Communication of the slave with a Class 2 master
Redundancy Not supported
Repeater Control Signal RS485 signal
Implementation Type SPC3