Installation Manual Manual

Publication CNET-IN003A-EN-P - January 2006
Install a ControlNet Ex Media System 3-27
Connect Devices
After you terminate your segments, connect your devices.
1. Remove and save the blue dust cap (on the straight or
right-angle connector).
2. Replace the dust cap with the blue intrinsically-safe insulator
ring.
3. Connect the straight or right-angle connector to your device.
To Connect a See
Fiber repeater hub Page 3-11
ControlNet Ex adapter Procedure below
If Your Node Supports Connect the Straight or Right-angle Connector
non-redundant media To the channel A connector on the device (channel B is not
used)
1
redundant media From trunk cable A to channel A on your device
From trunk cable B to channel B on your device
1
While both channels are active, we recommend using channel A for non-redundant media.