Plan a ControlNet Ex Media System 2-17
Order Components
Now that you are ready to begin ordering components, use these
guidelines to help you select components.
General Planning
The ControlNet Ex cable system is isolated from earth and must be
protected from inadvertent ground connections.
Plan a Segment
Refer to this list when you plan a segment.
All connections to the trunk cable require a tap
Taps may be installed at any location on the trunk cable
Tap drop-cable length must not be changed
Maximum number of taps = 48, with 250 m (820 ft) of standard
RG-6 trunk cable
Maximum trunk cable length of RG-6 trunk cable = 1000 m
(3280 ft), with 2 taps
75 trunk terminators are required on both ends
One tap with an unconnected drop cable may be installed for
maintenance purposes
Use BNC bullet connectors at future tap locations
Do not mix redundant and non-redundant nodes
Use ControlNet Ex tap terminators (1797-TCAP) for all other
unconnected drop cables
Avoid high noise environments when routing cables
A supplied ferrite toroid should be used on the ControlNet Ex
trunk as it enters and leaves control cabinets