User Manual

FLEX Ex I/O 24V DC 4 Non-Isolated Source Output Module 25
Publication
1797-5.6 - June 2011
FM C1. No.3600:1998, Electrical Equipment for Use in Hazardous
(Classified) Locations General Requirements
FM C1
. No.3610:1999, Intrinsically Safe Apparatus and Associated
Apparatus for Use in Class I, II, III Division 1 Hazardous (Classified)
Locations
FM C1. No
.3615:1989, Explosionproof Electrical Equipment General
Requirements
FM C1
. No.3810:1989, 1995, Electrical and Electronic Test,
Measuring and Process Control Equipment
ANSI/NEMA 250
, 1991, Enclosures for Electrical Equipment
Wiring Methods
Wi
ring method 1: Each channel is wired separately.
Wiring method 2: Multiple channels in one cable, providing each
channel is separated in accordance with the National Electric Code
(NEC).
Wiring Method
Wiring
Method
Channel Terminals V
oc
(V)
I
sc
(mA)
V
t
(V)
I
t
(mA)
Groups C
a
(μF)
L
a
(mH)
1 and 2 Any one
channel
(fo
r
example,
ch0)
0(+), 1(-) 27.4 110.0 - - A, B 0.105 3.0
C, E 0.315 9.0
D, F, G 0.840 24.0