2-8 Understanding Configurable FLEX Ex Thermocouple/RTD/mV Input Module Features
Underrange Alarm
The channel underrange alarm is set if the input is less than the
minimum temperature (thermocouple or RTD range dependent),
millivolt (-40mV) or resistance (0Ω) range value.
Range: 0 = normal, 1 = input overrange. Default = 0.
This alarm stays active at any value below 0% of range and is always
enabled by the module.
Range: 0 = normal, 1 = input overrange. Default = 0.
normal signal range
overrange
CJC fault
underrange
-200C +870C
IEC PT100
~ 520ohm equivalent
PHYSICAL INPUT SIGNAL RANGE
Sensor Type
-200C +400C
IEC PT200
-200C +630C
JIS PT100
-200C +400C
JIS PT200
-60C +250C
DIN Ni100
-60C +200C
DIN Ni200
-80C +320C
Minco Ni120
-200C +260C
Minco Cu10
0ohm 500ohm
0-500 Resistance
-40mV +100mV
millivolt ~ 210mV
300C +1800C
B
-250C +1000C
E
-210C +1200C
J
-250C
+1372C
K
-200C +800CTXK/XK(L)
-250C +1300C
N
0C
+1768C
R
0C
+1768C
S
-250C +400C
T
Channel
Data
Forced
to
Maximum
for Type
-20C 100C
Cold Junction Compensation
CJC fault
open wire fault
~ 520ohm equivalent
~ 520ohm equivalent
~ 520ohm equivalent
~ 520ohm equivalent
~ 520ohm equivalent
~ 520ohm equivalent
~ 520ohm equivalent
~ 520ohm
~ 210mV equivalent
~ 210mV equivalent
~ 210mV equivalent
~ 210mV equivalent
~ 210mV equivalent
~ 210mV equivalent
~ 210mV equivalent
~ 210mV equivalent
~ 210mV equivalent
IRT8 Specific alarming performance