User Manual User Manual

Rockwell Automation Publication 1794-UM010D-EN-E - July 2013 27
Install Your FLEX I/O VHSC Module
Input B
20 28
Input Z 21 29
Input Z 22 30
Outputs
Output Sourcing Out Return Output Sourcing Out Return
O0 6 23 O1 7 24
O2 14 31 O3 15 32
+24V DC
Base power
Terminals 34 and 50
+24V DC COM Terminals 35 and 51
+5V or +24V
Output power
Terminals 37 and 46
-V Output power Terminals 39 and 48
Chassis GND Terminals 16, 33, and 40…45
ATTENTION: Total current draw through the terminal base unit is
limited to 10 A. Separate power connections to the terminal base unit
may be necessary.
Wiring connections for the 1794-VHSC High Speed Counter Module