User Manual Manual

Publication 1794-6.5.12 - September 2011
38 Read and Write Configuration Maps for the FLEX I/O Module
Using Series A
Functionality in a
Series B Module
To employ Series A functionality when using a Series B 1794-IRT8 module,
connect a wire from terminal 39 to terminal 48 on the 1794-TB3G or
1794-TB3GS terminal base unit. When terminals 39 and 48 are wired together,
bit 4 in read word 9 will not be set (0), indicating the module is in Series A
functionality.
Chapter Summary
This chapter provided the user with data and instructions to configure and
map data for the FLEX I/O Thermocouple, RTD, and Millivolt Input
module.
Write Word 3 00…07 Extended data table data bits – These bits are written to the module during calibration. They are
used to define offset, gain and general channel calibration.
08…14
(10…16)
Extended data table command bits These bits are written to the module during calibration. They
are used to select channel calibration action.
15 (17) Reserved for factory use only
Bit/Word Descriptions for Block Transfer Write Words
Word Dec. Bits
(Octal Bits)
Description
ATTENTION
If these terminals are not connected together, the Series B
product will default to Series B functionality.