Instruction Manual

Publication 1794-6.5.8 - January 2010
Writing Configuration to and Reading Status from Your Module with a Remote I/O Adapter 71
1 0 1 0 0–10V binary 0% Under, 2%
Over
0000–F9C2> 0000–63938> 2.5ms 2.5ms
1 0 1 1 0–5V binary 0% Under, 4%
Over
0000–F3CF> 0000–62415> 2.5ms 2.5ms
1 1 0 0 ±20mA offset binary, 8000H =
0mA
4% Under, 4%
Over
<0618–F9E8> <1560–63976> 2.5ms 2.5ms
1 1 0 1 4–20mA offset binary, 8000H =
4mA
4% Under, 4%
Over
<8000–F878> <32768–63608> 7.5ms 5.0ms
1 1 1 0 ±10V offset binary, 8000H =
0V
2% Under, 2%
Over
<031F–FCE1> <799–64737> 2.5ms 2.5ms
1 1 1 1 ±5V offset binary, 8000H =
0V
4% Under, 4%
Over
<0618–F9E8> <1560–63976> 2.5ms 2.5ms
(1)
Underrange for 4-20mA occurs in the blind area below 0 (3.2mA).
(2)
< and > indicate the overrun beyond actual range (about 5%).
Table 4.15
Configuring Your Input Channels
Table 4.16
Setting the Input Filter
Bits Channel
03 02 01 00 Input Channel 0
07 06 05 04 Input Channel 1
A/D Conversion
Rate
Low Pass Filter
0 0 0 0 1200Hz No low pass
0 0 0 1 1200Hz 100ms low pass
0 0 1 0 1200Hz 500ms low pass
0 0 1 1 1200Hz 1000ms low pass
0 1 0 0 600Hz No low pass
0 1 0 1 600Hz 100ms low pass
0 1 1 0 600Hz 500ms low pass
0 1 1 1 600Hz 1000ms low pass
1 0 0 0 300Hz No low pass
1 0 0 1 300Hz 100ms low pass
1 0 1 0 300Hz 500ms low pass
1 0 1 1 300Hz 1000ms low pass
1 1 0 0 150Hz No low pass
1 1 0 1 150Hz 100ms low pass
1 1 1 0 150Hz 500ms low pass
1 1 1 1 150Hz 1000ms low pass