0 1 0 1 4-20mA signed 2’s complement % 4% Under, 4% Over <0–10000> <0–10000> 7.5ms
0 1 1 0 0–10V signed 2’s complement % 0% Under, 2% Over 0–10000> 0–10000> 5.0ms
0 1 1 1 +10V signed 2’s complement % 2% Under, 2% Over
<–10000–10000>
<–10000–10000> 5.0ms
1 0 0 0 0–20mA binary 0% Under, 4% Over 0000–F3CF> 0000–62415> 2.5ms
1 0 0 1
4–20mA
(1)
binary 4% Under, 4% Over 0000–F0F1> 0000–61681> 7.5ms
1 0 1 0 0–10V binary 0% Under, 2% Over 0000–F9C2> 0000–62415> 2.5ms
1 0 1 1 0–5V binary 0% Under, 4% Over 0000–F3CF> 0000–62415> 2.5ms
1 1 0 0 +20mA offset binary, 8000H = 0mA 4% Under, 4% Over <0618–F9E8> <32768–63976> 2.5ms
1 1 0 1 4–20mA offset binary, 8000H = 4mA 4% Under, 4% Over <8000–F878> <32768–63608> 7.5ms
1 1 1 0 +10V offset binary, 8000H = 0V 2% Under, 2% Over <031F–FCE1> <1560–63976> 2.5ms
1 1 1 1 +5V offset binary, 8000H = 0V 4% Under, 4% Over <0618–F9E8> <1560–63976> 2.5ms
(1)
Underrange for 4-20mA occurs in the blind area below 0 (3.2mA).
Table 6.9
Configuring Your Input Channels
Table 6.10
Setting the Input Filter
Bits Channel
03 02 01 00 Input Channel 0
07 06 05 04 Input Channel 1
A/D Conversion
Rate
Low Pass Filter
0 0 0 0 1200Hz No low pass
0 0 0 1 1200Hz 100ms low pass
0 0 1 0 1200Hz 500ms low pass
0 0 1 1 1200Hz 1000ms low pass
0 1 0 0 600Hz No low pass
0 1 0 1 600Hz 100ms low pass
0 1 1 0 600Hz 500ms low pass
0 1 1 1 600Hz 1000ms low pass
1 0 0 0 300Hz No low pass
1 0 0 1 300Hz 100ms low pass
1 0 1 0 300Hz 500ms low pass
1 0 1 1 300Hz 1000ms low pass
1 1 0 0 150Hz No low pass
1 1 0 1 150Hz 100ms low pass
1 1 1 0 150Hz 500ms low pass
1 1 1 1 150Hz 1000ms low pass