Mounting Dimensions
Environmental Conditions
Temperature,
operating
IEC 60068-2-1 (Test Ad, Operating Cold),
IEC 60068-2-2 (Test Bd, Operating Dry Heat),
IEC 60068-2-14 (Test Nb, Operating Thermal Shock):
0…55 °C (32…131 °F)
Temperature,
surrounding air, max
55 °C (131 °F)
Temperature,
nonoperating
IEC 60068-2-1 (Test Ab, Un-packaged Non-operating Cold),
IEC 60068-2-2 (Test Bb, Un-packaged Non-operating Dry Heat),
IEC 60068-2-14 (Test Na, Un-packaged Non-operating Thermal
Shock):
-40…85 °C (-40…185 °F)
Relative humidity IEC 60068-2-30 (Test Db, Un-packaged
Damp Heat):
5…95% non-condensing
Vibration IEC60068-2-6 (Test Fc, Operating):
5 g @ 10…500 Hz
Shock, operating IEC60068-2-27 (Test Ea, Unpackaged shock):
30 g
Shock, nonoperating IEC60068-2-27 (Test Ea, Unpackaged shock):
50 g
Emissions CISPR 11:
Group 1, Class A (with appropriate enclosure)
ESD immunity IEC 61000-4-2:
8 kV air discharges
Radiated RF immunity IEC 61000-4-3:
10 V/m with 1 kHz sine-wave 80%AM from 80…2000 MHz
10 V/m with 200 Hz 50% Pulse 100%AM at 900 MHz
10 V/m with 200 Hz 50% Pulse 100%AM at 1890 MHz
3 V/m with 1 kHz sine-wave 80%AM from 2000…2700 MHz
EFT/B immunity IEC 61000-4-4:
±2 kV at 5 kHz on power ports
±2 kV at 5 kHz on communications ports
Surge Transient
Immunity
IEC 61000-4-5:
±2 kV line-earth(CM) on communications ports
Conducted RF
Immunity
IEC 61000-4-6:
10 Vrms with 1 kHz sine-wave 80%AM from 150 kHz…80 MHz
Certifications (when product is marked)
(1)
c-UL-us UL Listed Industrial Control Equipment, certified for US and Canada.
See UL File E65584.
UL Listed for Class I, Division 2 Group A,B,C,D Hazardous Locations,
certified for U.S. and Canada. See UL File E194810.
CSA CSA Certified Process Control Equipment. See CSA File LR54689C.
CSA Certified Process Control Equipment for Class I, Division 2
Group A,B,C,D Hazardous Locations. See CSA File LR69960C.
CE European Union 2004/108/EC EMC Directive, compliant with:
EN 61326-1; Meas./Control/Lab., Industrial Requirements
EN 61000-6-2; Industrial Immunity
EN 61000-6-4; Industrial Emissions
EN 61131-2; Programmable Controllers (Clause 8, Zone A & B)
C-Tick Australian Radiocommunications Act, compliant with:
AS/NZS CISPR 11; Industrial Emissions
Ex European Union 94/9/EC ATEX Directive, compliant with:
EN 60079-15; Potentially Explosive Atmospheres, Protection "n"
EN 60079-0; General Requirements
II 3 G Ex nA IIC T4 X
Publications Installation Instructions 1794-IN098; User Manual 1794-UM009
(1)
See the Product Certification link at www.ab.com for Declarations of Conformity, Certificates, and other certification
details.
Mounting Dimensions
(3.4)
87
(0.83)21
(1.4)
35
(2.3)
59
(2.0)
50
(1.2)
28
(2.7)
69
(3.4H x 2.7W x 2.7D)
87H x 69W x 69D
1794-ASB/E
1794-ASB2/D
(inches)
millimeters
(3.4)
87
A
B
C
A = Mounting hole dimensions for optional mounting kit
B = DIN rail