Installation Instructions FLEX I/O ControlNet Redundant Media Adapter (Cat. No.
FLEX I/O ControlNet Redundant Media Adapter European Union Directive Compliance If this product has the CE mark it is approved for installation within the European Union and EEA regions. It has been designed and tested to meet the following directives.
FLEX I/O ControlNet Redundant Media Adapter 3 1. Position the ControlNet adapter module (A) on a 35 x 7.5mm DIN rail (B) (A-B pt. no. 199-DR1; 46277-3; EN 50022) at a slight angle. 2. Hook the lip on the rear of the adapter (A) onto the top of the DIN rail (B), and rotate the adapter module onto the rail. 3. Press the adapter module down onto the DIN rail until flush. Locking tab (C) will snap into position and lock the adapter module to the DIN rail. 4.
FLEX I/O ControlNet Redundant Media Adapter Wiring C A B G E D F 1. Connect the ControlNet network cable to connector, terminal A. 2. Connect the redundant ControlNet network cable to connector B. 3. Connect 24V common to the left side of the upper connector, terminal C. 4. Connect +24V dc input to the left side of the lower connector, terminal D. 5. Connections E and F are used to pass 24V dc power (F) and 24V common (E) to the next module in the series (if required). 6.
FLEX I/O ControlNet Redundant Media Adapter Comm B Comm A Status Indicators 5 Status Probable Cause Comm A and Comm B Simultaneously Off No power, or reset Red Adapter inoperative Red/Grn – (flashing alternately) Adapter self-test Red/Off – (flashing alternately) Bad node configuration (duplicate address) Comm A or Comm B (individually) Off Channel disabled Green Channel operational Flashing Grn/Off Temporary network errors Flashing Red/Off Cable fault, broken cable, redundancy warning
FLEX I/O ControlNet Redundant Media Adapter Power Supply Note: In order to comply with CE Low Voltage Directives, you must use a Safety Extra Low Voltage (SELV) or a Protected Extra Low Voltage (PELV) power supply to power this adapter. Input Voltage Rating 24V dc nominal Input Voltage Range 19.2V to 31.
FLEX I/O ControlNet Redundant Media Adapter Wiring Terminal Screw Torque Requirement 7-9 inch-pounds Agency Certification (when product or packaging is marked) • CSA certified • CSA Class I, Division 2 Groups A, B, C, D certified • UL listed • CE marked for all applicable directives 7 1 Use this conductor category information for planning conductor routing. Refer to publication 1770-4.1, “Industrial Automation Wiring and Grounding Guidelines.” Mounting Dimensions Inches (Millimeters) B 2.0 (50) 3.
FLEX I/O ControlNet Redundant Media Adapter With major offices worldwide. World Headquarters, Allen-Bradley, 1201 South Second Street, Milwaukee, WI 53204 USA, Tel: (1) 414 382-2000 Fax: (1) 414 382-4444 Publication 1794-5.18 – September 1996 PN955117–39 Copyright 1996 Allen-Bradley Company, Inc. Printed in USA Publication 1794-5.