Installation Instructions ArmorBlock MaXum 8 Input Module with 8 Connectors, Series B (Cat. No. 1792D-8BV0D) 42761 This ArmorBlock MaXum I/O module (Cat. No. 1792D-8BV0D) is a stand-alone 24V dc I/O product which communicates via a DeviceNet network. The sealed housing of this module requires no enclosure. This model has 8 inputs. Inputs are 24V dc automatically configured for PNP (sourcing) or NPN (sinking) devices.
ArmorBlock MaXum 8 Input Module with 8 Connectors, Series B Package Contents Your package contains: • 1 ArmorBlock MaXum Module • Installation Instructions (Note: Cable bases are ordered and shipped separately.) European Union Directive Compliance If this product has the CE mark it is approved for installation within the European Union and EEA regions. It has been designed and tested to meet the following directives.
ArmorBlock MaXum 8 Input Module with 8 Connectors, Series B 3 Install Your ArmorBlock MaXum I/O Module To install module: • • • • Set the node address Mount the module to the cable base Connect the cord sets Communicate with the module Set the Node Address Valid node addresses are 00 to 63. Set the node address using the rotary switches, RSNetWorx for DeviceNet, DeviceNetManager, or other software configuration tool. Setting the switches between 64 to 99 lets the software have address control.
ArmorBlock MaXum 8 Input Module with 8 Connectors, Series B The module is equipped with AutoBaud detect. AutoBaud lets the module read the settings already in use on your DeviceNet network and automatically adjusts to follow those settings. Install the Module This module mounts to the following cable bases: • • • • 1792D-CBFM for KwikLink™ flat media installation 1792D-CB12 for 12mm drop cable installation 1792D-CB18 for round media trunk connection or other optional cable base assembly.
ArmorBlock MaXum 8 Input Module with 8 Connectors, Series B 5 Note: Dimensions change according to the cable base and module combination used. 2.7 (68.6) 6.85 (174mm) Assembled dimensions in (mm) Align the screws to properly assemble the module to the base. 1.9 (48.26) Cable Base 1792D-CBFM is used for this example. 42762 Connect the Input Cord Sets to the MaXum Module This module uses 5 pin micro (12mm) style PCB mounted connectors. Eight micro caps cover the connectors on your module.
ArmorBlock MaXum 8 Input Module with 8 Connectors, Series B Please refer to publication 889-CP001A-EN-P and 889-TD001A-EN-P for Rockwell Automation cables and cord sets offerings. IMPORTANT If the devices (sensors) connected to the input connections require Class 2 power to operate, the DeviceNet connections of this equipment must be powered by a Class 2 source. • Make sure all connectors and caps are securely tightened to properly seal the connections against leaks and maintain IP67 requirements.
ArmorBlock MaXum 8 Input Module with 8 Connectors, Series B 7 DeviceNet Cables DeviceNet cables are described in the installation publications for the cable base assembly of your choice. Refer to the following publications: • 1792D-IN009B-EN-P ArmorBlock MaXum Cable Base Installation Guide • DN-6.7.
ArmorBlock MaXum 8 Input Module with 8 Connectors, Series B Byte Bit Description Produces 0 00-07 Input Status bits: When the bit is set (1), the input is on. Bit 00 = input 0, bit 01 = input 1, bit 02 = input 2, bit 03 = input 3, bit 04 = input 4, bit 05 = input 5, bit 06 = input 6, bit 07 = input 7. Produces 1 00-07 Sensor source voltage, input short circuit (ISC): Fault bits are set (1) when the sensor source voltage is faulted.
ArmorBlock MaXum 8 Input Module with 8 Connectors, Series B Troubleshoot with the Indicators This module has the following indicators: • Network and Module status indicator • Logic status indicator • Individual I/O status indicators for inputs 0 through 7.
ArmorBlock MaXum 8 Input Module with 8 Connectors, Series B Net/Mod Status Indicator (continued) Solid Red Unrecoverable fault Communication failure - duplicate node address present or incorrect baud rate Green to Red to Off At powerup only - LED test The following table describes logic status indicators.
ArmorBlock MaXum 8 Input Module with 8 Connectors, Series B 11 Hazardous Location Approval The following information applies only to products marked with Hazardous Location Approval, when operating in hazardous locations: Products marked “CL I, DIV 2, GP A, B, C, D” are suitable for use in Class I Division 2 Groups A, B, C, D, Hazardous Locations and nonhazardous locations only. Each product is supplied with markings on the rating nameplate indicating the hazardous location temperature code.
ArmorBlock MaXum 8 Input Module with 8 Connectors, Series B WARNING ÿ When used in a Class I, Division 2, hazardous location, this equipment must be mounted in a suitable enclosure with proper wiring method that complies with the governing electrical codes.
ArmorBlock MaXum 8 Input Module with 8 Connectors, Series B 13 AVERTISSEMENT ÿ AVERTISSEMENT ÿ Utiliser des fils d’alimentation qui conviennent à une température de 30°C au-dessus de la température ambiante. Pour une utilisation en environnement de classe i, division 2 dangereux, cet equipement doit etre monte dans un boitier avec un cablage approprie conforme aux normes electriques en vigueur. This product has been tested at an Open DeviceNet Vendor Association, Inc.
ArmorBlock MaXum 8 Input Module with 8 Connectors, Series B Specifications 8 Input Module - Cat. No. 1792D-8BVOD Input Specifications Max. Inputs per block 8 - 3 wire or dry contact PNP or NPN devices or 8 4 wire PNP or NPN devices Min. Sensor Source Current (per input) 50mA On-state Voltage 25V dc 10V dc On-state Current 10mA 2mA Off-state Voltage 5V dc - Off-state Current - 1.5mA Off-Wire Sense Current 0.
ArmorBlock MaXum 8 Input Module with 8 Connectors, Series B Notes: Publication 1792D-IN051A-EN-P - February 2001 15
Allen-Bradley is a registered trademark of Rockwell Automation. ArmorBlock, ArmorBlock MaXum, DeviceNetManager and KwikLink are trademarks of Rockwell Automation. DeviceNet is a trademark of Open DeviceNet Vendor Association. RSNetWorx for DeviceNet is a trademark of Rockwell Software, Inc. Publication 1792D-IN051A-EN-P - February 2001 PN 957485-03 © 2001 Rockwell International Corporation.