User guide

ArmorBlock MaXum 8 Input / 8 Output Module With Ground Lug 15
Publication
1792D-IN055A-EN-P - October 2004
The following table describes individual I/O status indicators.
Specifications
I/O Status Indicators
Function Module Status Indicator Point
Indicator
1
Status
Outputs Green
Green
Module Status blink red
Module Status blink red
Module Status blink red
Module Status blink red
None
Yellow
Orange
Red
Orange
Red
Output not energized
Output energized
Output shorted - auto restart
Output shorted - latching
Output no load - auto restart
Output no load - latching
Inputs Green
Green
Module Status blink red
Module Status blink red
None
Yellow
Red
Blink red
No valid input
Valid input
Short on input connector
1
Off wire on input connector
1
Only the first LED of each input connector will light as red when twin inputs are used.
8 Input / 8 Output Module - Cat. No. 1792D-8BVT8PE
Input Specifications Maximum Minimum
Inputs per block 8 - 3 wire or dry contact PNP devices or 4 - 4 wire PNP devices
Sensor Source Current (per connector) 100mA total -
Off-wire Sense Current 0.5mA -
On-state Voltage 25V dc 10V dc
On-state Current 10mA 2mA
Off-state Voltage 5V dc -
Off-state Current - 1.5mA
Output Specifications Maximum Minimum
Outputs per block 8 sourcing outputs labeled O0 through O7
Off Peak Blocking Voltage 30V 10V
On-state Voltage Drop 1V -
On-state Current 0.5A -
Off-state Leakage 1.5mA -
Module Current (all outputs) 4.0A -
Surge Current - for 10ms, repeatable
every 2s
2.4A -
No Load Sense Current (On-state) 0.18A -