The following table describes the network and module status
indicator.
The following table describes the logic status indicator.
The following table describes the auxiliary power indicator.
Net/Mod Status Indicator
Indicator Status
Off No power or auto bauding
Flashing Green/Off On line but not connected
Solid Green On line, link OK, connected
Flashing Red Recoverable fault - module configuration error
I/O connection fault - one or more I/O connections in the timed-out state
Solid Red Unrecoverable fault
Communication failure - duplicate node address present or incorrect
baud rate
Green to Red to Off At powerup only - LED test
Logic Status Indicators
Indicator Status
Off Logic is disabled
Solid Green Logic is enabled
Flashing Green Local forces are applied and local logic is enabled
Auxiliary Power
Indicator Status
None No auxiliary Power
Solid Green Auxiliary Power Present