Installation Instructions High Current 8 Input/8 Output ArmorBlock I/O Module Series B (Cat. No. 1792D-88HC) 41945 The High Current ArmorBlock™ I/O module (Cat. No. 1792D-88HC) is a stand-alone 24V dc I/O product which communicates via a DeviceNet™ network. The semi-sealed housing requires no enclosure. This module has 8 inputs and 8 outputs. Inputs are 24V dc PNP (sourcing) or NPN (sinking) devices. Outputs are self-protected 24V dc and are for sourcing only.
High Current 8 Input/8 Output ArmorBlock I/O Module Series B Important User Information Because of the variety of uses for the products described in this publication, those responsible for the application and use of these products must satisfy themselves that all necessary steps have been taken to assure that each application and use meets all performance and safety requirements, including any applicable laws, regulations, codes and standards.
High Current 8 Input/8 Output ArmorBlock I/O Module Series B IMPORTANT ATTENTION ! 3 Identifies information that is critical for successful application and understanding of the product. Environment and Enclosure This equipment is intended for use in a Pollution Degree 2 industrial environment, in overvoltage Category II applications (as defined in IEC publication 60664-1), at altitudes up to 2000 meters without derating.
High Current 8 Input/8 Output ArmorBlock I/O Module Series B Install Your High Current I/O Module To install the module you must: • • • • • Set the node address Mount the module Connect the cable assembly to the module Connect the DeviceNet cable to the module Communicate with your ArmorBlock I/O module More detailed information about each of these steps is in the following procedures.
High Current 8 Input/8 Output ArmorBlock I/O Module Series B 5 The two switches are: • MSD (most significant digit) • LSD (least significant digit) To reset the node address, use a small blade screwdriver to rotate the switches. Line up the small arrow on the switch with the number setting you wish to use. The rotary switches are read at module power up only. Settings between 64 and 99 cause the module to use the last valid node address stored internally. Example: The last setting was 40.
High Current 8 Input/8 Output ArmorBlock I/O Module Series B 3. Place screws through each of the 4 mounting holes and tighten the screws until the module is firmly in place. 7.74in. 196.6mm Side View 3.06in. 77.6mm Front View 41945 2.63in. 66.7mm 42288 Connect the Cable Assembly to the Module Inputs, outputs, and power can either be wired directly to a mating connector, or through a cable assembly.
High Current 8 Input/8 Output ArmorBlock I/O Module Series B 7 Connection Using a Prefabricated Harness Assembly 1. Connect the harness assembly, 1792D-88HCCBL, to field wiring. 2. Connect the harness connector to the module. The 1792D-88HC module connector pinout is shown below (looking into the module connector).
High Current 8 Input/8 Output ArmorBlock I/O Module Series B The following table lists the signal for each pin number.
High Current 8 Input/8 Output ArmorBlock I/O Module Series B 9 Connect the DeviceNet Cable to the Module Connect the DeviceNet wiring to the 5-pin micro-connector on the module. The micro-connector pinout is shown below.
High Current 8 Input/8 Output ArmorBlock I/O Module Series B Change-of-State - productions occur when an input changes or a fault condition occurs. If no input or fault condition change occurs within the expected packet rate, a heartbeat production occurs. This heartbeat production tells the scanner module that the I/O module is alive and ready to communicate. Consumption occurs when data changes and the master produces new input data to the I/O block.
High Current 8 Input/8 Output ArmorBlock I/O Module Series B 11 Troubleshoot with the Indicators This module has the following indicators: • Network/Module status indicator • Logic status indicators • Individual point status indicators The following illustration shows status indicators. Status Indicators 42287 The following table describes the network and module status indicator.
High Current 8 Input/8 Output ArmorBlock I/O Module Series B The following table describes the logic status indicator. Logic Status Indicators State Status Off Logic is disabled Solid Green Logic is enabled Flashing Green Local forces are applied and local logic is enabled The following table describes the I/O status indicator.
High Current 8 Input/8 Output ArmorBlock I/O Module Series B 13 Specifications 8 Input / 8 Output Module - Cat. No. 1792D-88HC Input Specifications Max. Inputs per block 8, Configurable as sinking or sourcing in two groups of 4 sourcing type is default Off-State Voltage 4 0 On-State Voltage 30 8 Off-State Current - 1.2mA On-State Current 11mA (@30V dc) 2mA (@10V dc) Output Specifications Max. Min. Outputs per block 8 sourcing type in two groups of 4 Off Peak Blocking Voltage Min.
High Current 8 Input/8 Output ArmorBlock I/O Module Series B General Specifications Operational Temperature IEC 60068-2-1 (Test Ad, Operating Cold), IEC 60068-2-2 (Test Bd, Operating Dry Heat), IEC 60068-2-14 (Test Nb, Operating Thermal Shock): –20 to 60°C (–4 to 140°F) Storage Temperature IEC 60068-2-1 (Test Ab, Un-packaged Non-operating Cold), IEC 60068-2-2 (Test Bb, Un-packaged Non-operating Dry Heat), IEC 60068-2-14 (Test Na, Un-packaged Non-operating Thermal Shock): –40 to 85°C (–40 to 185°F)
High Current 8 Input/8 Output ArmorBlock I/O Module Series B 15 General Specifications Agency Certification (when product is marked) c-UR-us CE 3 C-Tick3 ODVA Technical Data (user information) UL Recognized Component Industrial Control Equipment, certified for US and Canada European Union 89/336/EEC EMC Directive, compliant with: EN 50081-2; Industrial Emissions EN 50082-2; Industrial Immunity EN 61326; Meas./Control/Lab.
ArmorBlock and DeviceNetManager are trademarks of Rockwell Automation. RSNetWorx for DeviceNet is a trademark of Rockwell Software Inc. DeviceNetManager is a trademark of Rockwell Automation Allen-Bradley Inc. DeviceNet is a trademark of Open DeviceNet Vendor Association (ODVA). Publication 1792D-IN005D-EN-P - February 2002 Supersedes Publication 1792D-IN005C-EN-P - February 2001 PN 957678-04 Copyright © 2002 Rockwell Automation. All rights reserved. Printed in the U.S.A.