Installation Instructions ArmorBlock MaXum 2 Input Module Series B (Cat. No. 1792D-2BV0D) 41525 This ArmorBlock MaXum™ I/O module (Cat. No. 1792D-2BV0D) is a stand-alone 24V dc I/O product which communicates via a DeviceNet™ network. The sealed housing of this module requires no enclosure. This module has 2 inputs. Inputs are 24V dc PNP (sourcing) or NPN (sinking) devices. Diagnostic features included are short circuit and open wire detection reported to the point level.
ArmorBlock MaXum 2 Input Module Series B Package Contents Your package contains: • 1 ArmorBlock MaXum Module • Installation Instructions (Please note: Cable bases are ordered and shipped separately.) European Union Directive Compliance If this product has the CE mark it is approved for installation within the European Union and EEA regions. It has been designed and tested to meet the following directives.
ArmorBlock MaXum 2 Input Module Series B 3 Install Your ArmorBlock MaXum I/O Module To install the module: • • • • Set the node address Mount the module to the cable base Connect the cord sets Communicate with the module Each of these procedures is explained in detail in the following procedures. Set the Node Address Valid node addresses are 00 to 63. Set the node address using the rotary switches, RSNetWorx for DeviceNet™, DeviceNetManager™, or other software configuration tool.
ArmorBlock MaXum 2 Input Module Series B Refer to the illustration of the node address below. Example: Node Address is set at 62, see small black dots. 30703-M The module is equipped with AutoBaud detect. AutoBaud lets the module read the settings already in use on your DeviceNet network and automatically adjusts to follow those settings.
ArmorBlock MaXum 2 Input Module Series B 5 To install the module: IMPORTANT Proper alignment of the screws is necessary to complete the connections between the module contacts and the cable contacts. 1. Position the module over the mounted cable base. Align the three captive screws in the module with the accepting receptacles in the base. 2. Tighten the screws with a torque of 8 inch-pounds to secure the module to the base. Note: Dimensions change according to the cable base and module combination used.
ArmorBlock MaXum 2 Input Module Series B Connect the Input Cord Sets to the MaXum Module This module uses 5 pin micro (12mm) style PCB mounted connectors. Two micro caps cover the connectors on your module. Remove the caps and connect your cord sets to the appropriate ports. Use the micro caps to cover and seal unused ports. A pinout diagram for the connectors is shown next.
ArmorBlock MaXum 2 Input Module Series B 7 I/O connectors for this module are shown below. Connector A Input 0 Connector B Input 1 41527 DeviceNet Cable DeviceNet cables are described in the installation publications for the cable base assembly of your choice. Refer to the following publications: • 1792D-IN009B-EN-P ArmorBlock MaXum Cable Base Installation Guide • DN-6.7.
ArmorBlock MaXum 2 Input Module Series B Communicate With Your ArmorBlock MaXum I/O Module This ArmorBlock module’s I/O is exchanged with the master through a poll, change-of-state, or cyclic connection. The module produces input data as follows: Type of I/O Connections Consumes Cyclic 0 Byte Produces 1 Bytes Polled 0 Byte 1 Bytes Change-of-State 0 Byte 1 Bytes Cyclic - allows configuration of the block as an I/O client.
ArmorBlock MaXum 2 Input Module Series B 9 The DeviceNet Network uses advanced network technology, producer/consumer communication, to increase network functionality and throughput. Visit our web site at http://www.ab.com/networks for producer/consumer technology information and updates. Troubleshoot with the Indicators This module has the following indicators: • Network/Module status indicator • Logic status indicators • Individual point status indicators for inputs 0 and 1.
ArmorBlock MaXum 2 Input Module Series B The following table describes network and module status indicators.
ArmorBlock MaXum 2 Input Module Series B 11 Specifications 2 Input Module - Cat. No. 1792D-2BV0D Input Specifications Max Inputs per block 2 - 3 wire or dry contact PNP or NPN devices Min Sensor Source Current (per input) 100mA - Off-Wire Sense Current 0.
ArmorBlock MaXum 2 Input Module Series B Hazardous Location Approval The following information applies only to products marked with Hazardous Location Approval, when operating in hazardous locations: Products marked “CL I, DIV 2, GP A, B, C, D” are suitable for use in Class I Division 2 Groups A, B, C, D, Hazardous Locations and nonhazardous locations only. Each product is supplied with markings on the rating nameplate indicating the hazardous location temperature code.
ArmorBlock MaXum 2 Input Module Series B WARNING ! 13 When used in a Class I, Division 2, hazardous location, this equipment must be mounted in a suitable enclosure with proper wiring method that complies with the governing electrical codes.
ArmorBlock MaXum 2 Input Module Series B AVERTISSEMENT ! AVERTISSEMENT ! Utiliser des fils d’alimentation qui conviennent à une température de 30°C au-dessus de la température ambiante. Pour une utilisation en environnement de classe i, division 2 dangereux, cet equipement doit etre monte dans un boitier avec un cablage approprie conforme aux normes electriques en vigueur.
ArmorBlock MaXum 2 Input Module Series B 15 This product has been tested at an Open DeviceNet Vendor Association, Inc. (ODVA) authorized independent test laboratory and found to comply with ODVA Conformance Test. Please contact the ODVA website (http://www.odva.
ArmorBlock, ArmorBlock MaXum and KwikLink are trademarks of Rockwell Automation. DeviceNet is a trademark of Open DeviceNet Vendor Association. DeviceNetManager is a trademark of Rockwell Automation Allen-Bradley, Inc. RSNetWorx for DeviceNet is a trademark of Rockwell Software, Inc. Publication 1792D-IN019B-EN-P - September 2000 Supersedes Publication 1792D-5-19 - October 1998 PN 957395-48 © 2000 Rockwell International Corporation.