Installation Instructions ArmorBlock MaXum 16 Input Module Series B (Cat. No. 1792D-16BVTOD) 30723-M This ArmorBlock MaXum I/O module (Cat. No. 1792D-16BVT0D) is a stand-alone 24V dc I/O product which communicates via a DeviceNet network. The sealed housing of this module requires no enclosure. This model has 16 inputs accessed through Y splitter cables. Inputs are 24V dc automatically configured for PNP (sourcing) or NPN (sinking) devices.
ArmorBlock MaXum 16 Input Module Series B Package Contents Your package contains: • 1 ArmorBlock MaXum Module • Installation Instructions (Please note: Cable bases are ordered and shipped separately.) European Union Directive Compliance If this product has the CE mark it is approved for installation within the European Union and EEA regions. It has been designed and tested to meet the following directives.
ArmorBlock MaXum 16 Input Module Series B 3 Install Your ArmorBlock MaXum I/O Module To install the module: • • • • Set the node address Mount the module to the cable base Connect the cord sets Communicate with the module Set the Node Address Valid node addresses are 00 to 63. Set the node address using the rotary switches, DeviceNetManager, RSNetWorx for DeviceNet, or other software configuration tool. Setting the switches between 64 to 99 lets the software have address control.
ArmorBlock MaXum 16 Input Module Series B The module is equipped with AutoBaud detect. AutoBaud lets the module read the settings already in use on your DeviceNet network and automatically adjusts to follow those settings.
ArmorBlock MaXum 16 Input Module Series B 5 Note: Dimensions change according to the cable base and module combination used. 2.7 (68.6) 6.85 (174mm) Align the screws to properly assemble the module to the base. 1.9 (48.26) Cable Base 1792D-CBFM is used for this example. Assembled dimensions in (mm) 30724-M Connect the Input Cord Sets to the MaXum Module This module uses 5 pole micro (12mm) style PCB mounted connectors. Eight micro caps cover the connectors on your module.
ArmorBlock MaXum 16 Input Module Series B IMPORTANT ATTENTION ! If the devices (sensors) connected to the input connections require Class 2 power to operate, the DeviceNet connections of this equipment must be powered by a Class 2 source. • Make sure all connectors and caps are securely tightened to properly seal the connections against leaks and maintain IP67 requirements. • For maximum noise immunity, input and output cable return wires must be properly terminated.
ArmorBlock MaXum 16 Input Module Series B 7 DeviceNet Cable DeviceNet cables are described in the installation publications for the cable base of your choice. Refer to the following publications: • 1792D-IN009B-EN-P ArmorBlock MaXum Cable Base Installation Guide • DN-6.7.2 DeviceNet Cable Planning and Installation Manual Communicate With Your ArmorBlock MaXum Module This ArmorBlock module’s I/O is exchanged with the master through a polled, change-of-state, or cyclic connection.
ArmorBlock MaXum 16 Input Module Series B Byte Bit Description Produces 0 00-07 Input status bits: When the bit is set (1), the input is on. Bit 00 = input 0, bit 01= input 1, bit 02 = input 2, bit 03 = input 3, bit 04 = input 4, bit 05 = input 5, bit 06 = input 6, bit 07 = input 7. Produces 1 00-07 Input status bits: Bit 00 = input 8, bit 01= input 9, bit 02 = input 10, bit 03 = input 11, bit 04 = input 12, bit 05 = input 13, bit 06 = input 14, bit 07 = input 15.
ArmorBlock MaXum 16 Input Module Series B 9 Troubleshoot with the Indicators This module has the following indicators: • Network and Module status indicator • Logic status indicator • Individual point status indicators for inputs 0, through 15 Point indicators for inputs 0 and 1 Connector A Point indicators for inputs 14 and 15 Connector H Point indicators for inputs 2 and 3 Connector B Point indicators for inputs 12 and 13 Connector G Point indicators for inputs 10 and 11 Point indicators for inputs
ArmorBlock MaXum 16 Input Module Series B The following table describes logic status indicators. Logic Status Indicators State Status Off Logic is disabled Solid Green Logic is enabled Flashing Green Local forces are applied and local logic is enabled The following table describes individual I/O status indicators.
ArmorBlock MaXum 16 Input Module Series B 11 Specifications 16 Input Module - Cat. No. 1792D-16BVTOD Input Specifications Max. Inputs per block 16 - 3 wire or dry contact PNP or NPN devices or 8 4 wire PNP or NPN devices Min. Sensor Source Current (per input) See graphic below. On-state Voltage 25V dc 10V dc On-state Current 10mA 2mA Off-state Voltage 5V dc - Off-state Current - 1.5mA Off-Wire Sense Current 0.
ArmorBlock MaXum 16 Input Module Series B 16 Input Module - Cat. No. 1792D-16BVTOD Input Specifications Max. Technical Data (user information) Publication 1792-TD001B-EN-P Min. Refer to the graph below for an illustration of sensor source current. 1.0 Temperature = 55°C Sensor Source Current (Amp) 0.8 Temperature = 60°C 0.6 0.4 Note: This is an illustration of total current for all 16 inputs. Divide by 16 for current per input. 0.2 0.
ArmorBlock MaXum 16 Input Module Series B 13 Hazardous Location Approval The following information applies only to products marked with Hazardous Location Approval, when operating in hazardous locations: Products marked “CL I, DIV 2, GP A, B, C, D” are suitable for use in Class I Division 2 Groups A, B, C, D, Hazardous Locations and nonhazardous locations only. Each product is supplied with markings on the rating nameplate indicating the hazardous location temperature code.
ArmorBlock MaXum 16 Input Module Series B WARNING ! When used in a Class I, Division 2, hazardous location, this equipment must be mounted in a suitable enclosure with proper wiring method that complies with the governing electrical codes.
ArmorBlock MaXum 16 Input Module Series B 15 AVERTISSEMENT ! AVERTISSEMENT ! Utiliser des fils d’alimentation qui conviennent à une température de 30°C au-dessus de la température ambiante. Pour une utilisation en environnement de classe i, division 2 dangereux, cet equipement doit etre monte dans un boitier avec un cablage approprie conforme aux normes electriques en vigueur. This product has been tested at an Open DeviceNet Vendor Association, Inc.
ArmorBlock, ArmorBlock MaXum, and KwikLink are trademarks of Rockwell Automation. RSNetWorx for DeviceNet is a trademark of Rockwell Software Inc. DeviceNetManager is a trademark of Rockwell Automation Allen-Bradley, Inc. DeviceNet is a trademark of Open DeviceNet Vendor Association. Publication 1792D-IN016B-EN-P - September 2000 Supersedes Publication 1792D-5.16 - January 1999 PN 957395-36 © 2000 Rockwell International Corporation.