Owner's manual

8 ArmorBlock MaXum 12 Input/ 4 Output Module With Ground Lug
Publication
1792D-IN056A-EN-P - October 2004
Refer to publication 889-5.0 for Rockwell Automation cables and cord
sets offerings.
WARNING
Use supply wires suitable for 30°C above
surrounding ambient.
IMPORTANT
If the devices (sensors) connected to the input
connections require Class 2 power to operate, the
DeviceNet connections of this equipment must be
powered by a Class 2 source.
ATTENTION
Make sure all connectors and caps are securely
tightened to properly seal the connections
against leaks and maintain IP67 requirements.
For maximum noise immunity, input and output
cable return wires must be properly terminated.
When inputs and outputs are connected in
loopback, return wires should be connected
together.
I/O cable length should be less than 30 meters.