Owner's manual

ArmorBlock-LP 8 Input/8 Output Module 9
Publication
1792-5.8 – December 1997
30197–M
NS = Network Status Indicator
OVL = Sensor and Output
Status Indicator
U
S
= Output Power
Supply Status Indicator
U
L
= Module Power Supply
Status Indicator
A and B = Input
and Output I/O
Status Indicators
MS = Module Status
Indicator
Output
Connector
OUTIN
1
2
34
5
6
7
8
A
B
A
B
A
B
A
B
A
B
A
B
A
B
A
B
Note: This
module contains a circuit to protect the DeviceNet power supply from short
circuits in an attached sensor or sensor cable. If you connect a sensor while the
module is powered, the surge current produced by the sensor can cause the
module to fault. This operation is normal.
Network Status Indicator NS
Indication Status
Flashing Green On-line, not connected
Solid Green Link OK, on-line connected
Flashing Red At least 1 I/O connection is in the timed-out state
Solid Red Incorrect baud rate, or a duplicate Mac ID exists
Module
Status Indicator MS
Indication Status
OFF
No power, or no network access
Flashing
Green/OFF
On-line but not connected
Solid Green On-line, link okay, connected
Flashing Red Recoverable fault
Solid Red Critical failure