Owner's manual

ArmorBlock-LP 8 Input/8 Output Module10
Publication
1792-5.8 – December 1997
Sensor
Short Circuit Indicator OVL
Indication Status
OFF Sensor source voltage operating correctly
Solid Red 1 or more Sensor source voltage shorts, output
overload or no load condition
Output
I/O Status Indicators A and B
Indication Status
OFF Output is off
Yellow Output is on
Input
I/O Status Indicators A and B
Indication Status
OFF No valid input signal present
Yellow Valid input signal present
Module
and Sensor Power Supply Status Indicators U
S
and U
L
Indication Status
OFF Power supply is not functioning correctly
Green Power Supply is operating
Specifications
8
Input/8 Output Module – Cat. No. 1792-IB8XOB8PLP
Input Specifications
Inputs per Block 8 sinking inputs labeled 1, 3, 5, and 7
On-state Voltage Range 12–30V dc
On-state Current Maximum
Minimum
15.0mA @ 30V dc
1.6mA @ 12V dc
Off-state Voltage Maximum 5V dc
Off-state Current Minimum 0.8mA
Transition Voltage 5–12.0V dc
Transition Current 0.8–2.2mA
Input Signal Delay
Off to On or On to Off 1ms maximum
Specifications continued on next page.