Instruction Manual
35
ArmorBlock 4 Input Module
Publication 1792-5.1 – October 1996
4
Input Module – Cat. No. 1792-IB4
General Specifications
DeviceNet Power Voltage
Current
11.0 – 25.0V dc
100mA (no powered sensors)
300mA (full sensor load)
Surge Current at Power Up Less than 10A for 5ms
Dimensions Inches
Millimeters
2.6H X 7.7W X 3.06D
66H X 195W X 77.7D
Connectors 1792-IB4A/B – Aluminum connectors
1792-IB4S/B – Stainless Steel Connectors
Power Dissipation Maximum 1.0 Watts
Thermal Dissipation Maximum 3.4 BTU/hr
Environmental Conditions
Operational Temperature
Storage Temperature
Relative Humidity
Shock Operating
Non-operating
Vibration
–25 to 70
o
C (–13 to 158
o
F)
–40 to 85
o
C (–40 to 185
o
F)
up to 100%
30 g peak acceleration, 11(+
1)ms pulse width
50 g peak acceleration, 11(+
1)ms pulse width
Tested 10 g @ 10–500Hz per IEC 68-2-6
Conductors Refer to publication 1485-6.7.1 for information
on cabling for your DeviceNet module.
Enclosure Meets or exceeds NEMA 4X and 6P, IP67
1200psi, 140
o
F hosedown
Agency Certification
(when product or packaging is marked)
• CSA certified
• CSA Class I, Division 2, Groups A, B, C, D
certified
• UL listed
• CE marked for all applicable directives
This
product has been tested at an Open DeviceNet V
endor Association,
Inc. (ODV
A) authorized independent test laboratory and found to comply
with ODVA Conformance Test Software V
ersion FT 1.2/1.0.