29
ArmorBlock 16 Input Module
Publication 1792-5.3 – October 1996
”This connection contains input data in bytes 0 and 1 and sensor source voltage status
at bit 7 of byte 2.”;
[ParamClass]
MaxInst = 21; $ 4 configurable and 17 read–only parameters.
Descriptor = 0x09; $ Stub param instances in eeprom.
CfgAssembly = 0x66; $ The config assembly is instance #102 of assy obj.
[Params]
$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$
$$$$$$$$$$
Param1 = $ Disable Autobaud
0, $ reserved
6, $ Link Path Size
”20 03 24 01 30 64”, $ Link Path to disable autobaud attribute.
0x0002, $ No support for settable path, scaling, scaling links, or
$ real time update of value. Value is gettable and
$ Settable. Enumerated strings are supported.
4, $ Data Type – boolean
1, $ Data Size
”Autobaud”, $ Parameter Name
””, $ Units String
$$$$$$$$$$ Help string $$$$$$$$$$$
”Enable takes effect after next powerup. Disable is required to set fixed baud rate, no
power cycle is required.”,
0,1,0, $ Min, Max, and Default values
1,1,1,0,0,0,0,0,0; $ Not Used
$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$
$$$$$$$$$$
Param2 = $ Input filter Off_to_On Delay selection
0, $ reserved
6, $ Link Path Size
”20 0F 24 02 30 01”, $ Link Path to param instance. The param instance
decodes
$ the enumerated parameter into engineering units (micro
seconds).
0x0002, $ No support for settable path, scaling, scaling links,
$ or real time update of value. Value is gettable and
$ Settable. Enumerated strings are supported.
2, $ Data Type – unsigned int
2, $ Data Size – (in bytes)
”Off–to–On Delay”, $ Parameter Name
”ms”, $ Units String
$$$$$$$$$$ Help string $$$$$$$$$$$
”Signal must be present for this delay period before module detects the change.”,
0,4,0, $ Min, Max (max enumeration #), and Default values
1,1,1,0,0,0,0,0,0; $ Not Used
$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$
$$$$$$$$$$
Param3 = $ Input filter On_to_Off Delay selection
0, $ reserved