Instruction Manual
CompactBlock Distributed I/O on Remote I/O 9
Publication 1791R-IN001A-EN-P - February 2002
Mount the Block(s)
The base and expansion modules mount to a panel or DIN rail which
must be grounded before installing the module(s).
Base Module Mounting
Install the CompactBlock base module on a panel or DIN rail.
Panel Mounting
1. Place the module against the panel where you want to mount
it.
2. Drill holes in the panel that are aligned with mounting holes
on the module.
DIP
Switch
No. Description ON OFF
SW2
1Comm Rate
00=57.6K 01=115.2K
10=230.4K 11=230.4K
2Comm Rate
3 N/A
4 Hold Last State Hold Last State Output Reset
5 Processor
Restart/Lockout
Lockout Restart
6 Last I/O Last Rack Not Last Rack
7 Filter Speed Setting
00=2ms 10=4ms
01=8ms 11=16ms
8 Filter Speed Setting
WARNING
!
When used in a Class I, Division 2, hazardous
location, this equipment must be mounted in a
suitable enclosure with proper wiring method
that complies with the governing electrical
codes.