Instruction Manual

CompactBlock Distributed I/O on PROFIBUS DP Series D 23
Publication
1791P-IN002B-EN-P - October 2003
Maximum Input Data Format (Base Modules -4B4P)
Bit Position
Word 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
0 Reserved In3 In2 In1 In0 Base
1 Reserved Analog Input Data Channel 0
2 Reserved Analog Input Data Channel 1
3 Reserved Analog Input Data Channel 2
4 Reserved Analog Input Data Channel 3
5 URo1 URo0 ORo1 ORo0 OW3 OW2 OW1 OW0 ORi3 ORi2 ORi1 ORi0 Reserved RF UF
UF Module Unrecoverable Fault Set “0”: No Error Set “1”: Error
RF Module Recoverable Fault Set “0”: No Error Set “1”: Error
ORi x Over Range Input Channel Set “0”: No Over Range Set “1”: Over Range
OW x Input Open Wire (@ 4-20mA Range) Set “0”: No Open Wire Set “1”: Open Wire
ORo x Output Data Over Range Set “0”: No Over Range Set “1”: Over Range
URo x Output Data Under Range (@4-20MA Range) Set “0”: No Under Range Set “1”: Under Range
Maximum Output Data Format (Base Modules -4B4P)
Word
Bit Position
15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
0 Reserved O3 O2 O1 O0 Base
1 Reserved Analog Output Data Channel 0
2 Reserved Analog Output Data Channel 1