Safety Modules Owner manual

Rockwell Automation Publication 1791ES-UM001D-EN-P - May 2013 95
Configuration Reference Information Appendix C
Table 32 - Safety and Standard Data
Data Description
Input data Safety Input Data Safety Indicates the ON/OFF status of each input circuit.
ON: 1
OFF: 0
Combined Safety Input Status Safety An AND of the status of all input circuits.
All circuits are normal: 1
An error was detected in one or more input circuits: 0
Individual Safety Input Status Safety Indicates the status of each input circuit.
Normal: 1
Fault (Alarm): 0
Combined Safety Output Status Safety An AND of the status of all safety output circuits.
All circuits are normal: 1
An error has been detected in one or more output circuits: 0
Individual Safety Output Status Safety Indicates the status of each safety output circuit.
Normal: 1
Fault (Alarm): 0
Muting Lamp Status Safety Indicates the status when circuit T3 is configured as the muting lamp output.
Normal: 1
Fault (Alarm): 0
Safety Output Monitor Standard Monitors the outputs of the safety output circuits.
ON: 1
OFF: 0
Individual Test Output Status Standard Indicates the status of each of the test output circuits.
Normal: 1
Fault (Alarm): 0
Output data Safety Output Data Safety Controls the safety output.
ON: 1
OFF: 0
Standard Output Data Standard Controls the test output when test output mode is set to a standard output.
ON: 1
OFF: 0