Safety Modules Owner manual

Rockwell Automation Publication 1791ES-UM001D-EN-P - May 2013 51
Configure the I/O Modules by Using the Logix Designer Application Chapter 5
Safety-Readback - This selection is not available for input-only safety
modules. Selecting Safety-Readback creates both safety and readback tags,
with readback indicating the presence of 24V on the output terminal.
Input Status Options
Choose from these options.
None - No status tags, only data for the inputs
IMPORTANT
Status data is not SIL 3 data. Do not use status data to directly control a SIL 3
safety output.