Safety Modules Owner manual

34 Rockwell Automation Publication 1791ES-UM001D-EN-P - May 2013
Chapter 3 Install and Connect Your Modules
Install the Module
IMPORTANT
Follow these instructions when installing a module.
Use the module in an environment that is within the general
specifications.
Use the module in an enclosure rated IP54 (IEC60529) or higher.
Use DIN rail that is 35 mm (1.38 in.) wide to mount the module in
the control panel.
Always use an end plate on each end of the module to secure it.
Place other heat sources an appropriate distance away from the
module to maintain ambient temperatures around the module
below specified maximums.
A 1791ES module can be installed either horizontally or vertically.