Instruction Manual
Module Calibration
Chapter 7
7-3
Table 7.D
Calibration
Block T
ransfer Read or Discrete Input Bit/Word Descriptions
Word Decimal
Bit
(Octal Bit)
Description
Bit 00
Input calibration error bit. When set, indicates input channel 0
calibration error.
Bit 01
Input calibration error bit. When set, indicates input channel 1
calibration error.
Bit 02
Input calibration error bit. When set, indicates input channel 2
calibration error.
Bit 03
Input calibration error bit. When set, indicates input channel 3
calibration error.
Bit 04
Output calibration error bit. When set, indicates output channel 0
calibration error.
Bit 05
Output calibration error bit. When set, indicates output channel 1
calibration error.
Word 0
Bit 06
High/Low bit HL. Indicates whether full scale or zero data point is
being updated:
Bit 6 = 1 - full scale
Bit 6 = 0 - zero data point
Bit 07
Calibration Done bit DN. When set (1), indicates calibration started
and selected channels updated.
Bit 08 (10)
Input Mode bit IM.
Bit 8 = 0 - Use for voltage inputs. Input scaling in mV
Bit 8 = 1 - Use for current inputs. Input scaling in µA
Bits 0910 (1112)
Not used.
Bit 11 (13)
EEPROM OK bit (OK). When set, indicates the calibration data has
been saved.
Bits 1215 (1417)
Calibration mode bits. Indicates the calibration sequence is selected.
Word 1 Bits 0015 (0017) Corrected Input Data for Channel 0 using most recent calibration data.
Word 2 Bits 0015 (0017) Corrected Input Data for Channel 1 using most recent calibration data.
Word 3 Bits 0015 (0017) Corrected Input Data for Channel 2 using most recent calibration data.
Word 4 Bits 0015 (0017) Corrected Input Data for Channel 3 using most recent calibration data.