Chapter 2
2-12
Power Supply Requirements
An external 24V dc (+10/-25%) power supply is required to power the
block. Total current required to power the block is equal to 300mA.
In addition, the external power supply should have current limiting
capabilities. The voltage range must not exceed 18.0-26.4V dc.
Wiring Requirements
Wiring cable requirements are shown in Table 2.J.
T
able 2.J
Acceptable
W
iring Cables for Block I/O Connection
Use Cable Type With
Remote I/O Link Belden 9463
PLC-2, PLC-3, PLC-5 family programmable
controllers and SLC controllers
Input and Output wiring
Up to 14AWG (2mm
2)
Stranded
with 3/64 inch (1.2mm) insulation
All
Figure 2.3
Remote
I/O Link W
iring
GROUP
No.
GROUP No.
2
(CLR)
Shield
1
(BLU)
24VDC
RET
24VDC
Connection
Clear
wire X
Blue wire X
Shield wire X
Chassis
GND
2
(CLR)
1
(BLU)
Shield
10928-I
-
150 OHM
- 82 OHM
-OFF
TERMINATION
RESISTOR