Installation Instructions DeviceNet Digital Base Terminal Block CompactBlock LDX I/O Catalog Numbers 1790D-T16BV0, 1790D-T8BV8V, 1790D-T8BV8B, 1790D-T0B16, 1790D-T0V16, 1790D-T0W6, 1790D-T8A0, 1790D-T0A6, Series B Topic Page Important User Information 2 Preventing Electrostatic Discharge 3 Environment and Enclosure 4 North American Hazardous Location Approval 5 Before You Begin 5 Install the Base Block 6 Set the Node Address 6 Mount the Base Block 7 Mount the Optional Expansion Block 9
DeviceNet Digital Base Terminal Block CompactBlock LDX I/O Important User Information Solid state equipment has operational characteristics differing from those of electromechanical equipment. Safety Guidelines for the Application, Installation and Maintenance of Solid State Controls (publication SGI-1.1 available from your local Rockwell Automation sales office or online at http://literature.rockwellautomation.
DeviceNet Digital Base Terminal Block CompactBlock LDX I/O 3 Preventing Electrostatic Discharge ATTENTION This equipment is sensitive to electrostatic discharge, which can cause internal damage and affect normal operation. Follow these guidelines when you handle this equipment: • Touch a grounded object to discharge potential static. • Wear an approved grounding wriststrap. • Do not touch connectors or pins on component boards. • Do not touch circuit components inside the equipment.
DeviceNet Digital Base Terminal Block CompactBlock LDX I/O Environment and Enclosure ATTENTION This equipment is intended for use in a Pollution Degree 2 industrial environment, in overvoltage Category II applications (as defined in IEC publication 60664-1), at altitudes up to 2000 meters (6562 ft) without derating. This equipment is considered Group 1, Class A industrial equipment according to IEC/CISPR Publication 11.
DeviceNet Digital Base Terminal Block CompactBlock LDX I/O 5 North American Hazardous Location Approval The following information applies when operating this equipment in hazardous locations: Informations sur l’utilisation de cet équipement en environnements dangereux: Products marked "CL I, DIV 2, GP A, B, C, D" are suitable for use in Class I Division 2 Groups A, B, C, D, Hazardous Locations and nonhazardous locations only.
DeviceNet Digital Base Terminal Block CompactBlock LDX I/O versions of the blocks. For example, for the EDS file for 1790D-T8BV8B blocks, use the EDS file labelled 1790D-8BV8B. Install the Base Block To install the base block: • • • • • set the node address on the base block. mount the base block. mount the optional expansion blocks. wire the terminal block. connect the DeviceNet cable.
DeviceNet Digital Base Terminal Block CompactBlock LDX I/O 7 Mount the Base Block Mount the base block to a panel or DIN rail. We recommend that you ground the panel or DIN rail before mounting the block. Dimensions 44251 95 mm (3.74 in.) 41 mm (1.6 in.) Expansion Cable Cover 16-point Base Module 95 mm (3.74 in.) 41 mm (1.6 in.
DeviceNet Digital Base Terminal Block CompactBlock LDX I/O Mount on a Panel For panel mounting, use these steps. 1. Place the block against the panel where you want it mounted. 2. Gently pull and position the expansion cover to the left. 3. Place a center punch, nail, or similar device through the mounting holes in the block and make two marks on the panel at the lower-left and upper-right corners of the module. 4.
DeviceNet Digital Base Terminal Block CompactBlock LDX I/O 9 3. Push up on the locking lever to secure the base block to the rail when the base block is flush against the rail. Mount the Optional Expansion Block To mount the optional expansion block, use these steps. 1. Mount the expansion block by connecting it to a previously-installed CompactBlock LDX I/O base or expansion block. 2. Beginning with the base block, mount your expansion block either horizontally or vertically.
DeviceNet Digital Base Terminal Block CompactBlock LDX I/O • To mount vertically (up or down), add an expansion block either up or down in a back-to-back configuration. In this configuration, you must use the optional 15 cm (5.9 in.) ribbon cable, catalog number 1790-15CMCBL, and alternately position the block in a right-side up, upside-down fashion. Right Side Up The longer expansion cable, catalog number 1790-15CMCBL, provides for up to 7 cm (2.76 in.) of space between blocks.
DeviceNet Digital Base Terminal Block CompactBlock LDX I/O 11 1790D-T16BVO Input Base Block Wiring Diagram IN0 IN2 IN1 IN4 IN3 IN6 COM0 COM1 IN8 IN5 IN7 IN10 COM0 COM1 IN9 IN12 IN11 IN14 IN13 IN15 44262 For inputs 0…7: For sinking inputs, wire COM 0 to Field Power (-) GND. For sourcing inputs, wire COM 0 to Field Power (+) 24V DC. For inputs 8…15: For sinking inputs, wire COM 1 to Field Power (-) GND. For sourcing inputs, wire COM 1to Field Power (+) 24V DC.
DeviceNet Digital Base Terminal Block CompactBlock LDX I/O 1790D-T8BV8B Input/Output Base Block Wiring Diagram IN0 IN2 IN1 IN3 IN4 IN6 IN5 COM IN7 VDC OUT0 OUT2 OUT4 OUT6 COM GND OUT1 OUT3 OUT5 OUT7 44264 For sinking inputs, wire COM to Field Power (-) GND. For sourcing inputs, wire COM to Field Power (+) 24V DC. Note that COM are internally connected. For sourcing outputs, wire V DC to Field Power (+) 24V DC, and wire GND to Field Power (-) GND.
DeviceNet Digital Base Terminal Block CompactBlock LDX I/O 13 1790D-TOV16 Output Base Block Wiring Diagram OUT0 OUT2 OUT4 OUT6 VDC0 VDC1 OUT1 OUT3 OUT8 OUT10 OUT12 OUT14 OUT5 OUT7 GND0 GND1 OUT9 OUT11 OUT13 OUT15 44182 For sinking outputs, wire V DC 0 (pin 9) and V DC 1 (pin 11) to Field Power (+) 24V DC, and wire GND0 (pin 10) and GND1 (pin 12) to Field Power (-) GND.
DeviceNet Digital Base Terminal Block CompactBlock LDX I/O 1790D-T8A0 AC Input Base Block Wiring Diagram VAC VAC IN0 COM COM IN1 IN2 IN3 IN4 IN5 COM COM COM COM COM IN6 IN7 COM COM COM 44267 Wire 120V AC Field Power to V AC and COM. Note that all V AC are internally connected. All COM are internally connected.
DeviceNet Digital Base Terminal Block CompactBlock LDX I/O 15 • 1799-DNC5MMS - 5-position open-style to 12 mm (0.47 in.) connector with locking screws WARNING If you connect or disconnect the communication cable with power applied to this module or any device on the network, an electrical arc can occur. This could cause an explosion in hazardous location installations. Be sure that power is removed or the area is nonhazardous before proceeding. 1.
DeviceNet Digital Base Terminal Block CompactBlock LDX I/O • I/O status If a module status indicator is flashing red, refer to the cable break procedures section. Status Indicators Indicator Status Description Module Solid red Unrecoverable fault in base unit. Replace base block. Flashing red Fault in expansion unit, or Node address switches do not match current node address. Reconnect or replace, as needed. Solid green Normal operation. Off No power. Apply power to device.
DeviceNet Digital Base Terminal Block CompactBlock LDX I/O 17 Status Indicators Indicator Status Description Network Solid red Module node number is a duplicate of an existing node, or network communication issues exist. Change module node number to an unused address, or verify network wiring is correct and communication is stable. Flashing red An I/O connection has timed out. Cycle power to the module.
DeviceNet Digital Base Terminal Block CompactBlock LDX I/O • Base and digital input expansion module • Digital input expansion module and another digital input expansion module All digital-expansion inputs produce data of 0 if the expansion cable is removed. No status is in the default produced assembly. Attribute 101 in the identity object reports module faults. If no faults are present, an explicit message GET command returns 0.
DeviceNet Digital Base Terminal Block CompactBlock LDX I/O 19 Specifications Universal DC Input Base Block - 1790D-T16BV0 Attribute Value Number of inputs 16 Input type Sink, source 24V DC Voltage, off-state input, max 5V DC Voltage, on-state input, max 28.8V DC Voltage, on-state input, nom 24V DC Voltage, on-state input, min 9.6V DC Current, off-state input, max 1.5 mA @ 5V DC Current, on-state input, max 8 mA @ 28.8V DC per channel Input impedance, nom 4.
DeviceNet Digital Base Terminal Block CompactBlock LDX I/O 1790D-TOV16, 1790D-TOB16 Attribute Value Output signal delay, off to on, max 0.5 ms Output signal delay, on to off, max 1.0 ms Output current rating, output, max 0.5 A Output current rating, common, max 4.0 A Field power dissipation 2.76 W @ 28.8V DC DC field power Supply voltage - 24V DC nom Voltage range - 10…28.
DeviceNet Digital Base Terminal Block CompactBlock LDX I/O 21 1790D-T8BV8V, 1790D-T8BV8B Attribute Value Output current rating, output, max 0.5 A Output current rating, common, max 4.0 A Leakage, off-state, max 0.5 mA Output signal delay, off to on, max 0.5 ms Output signal delay, on to off, max 1.0 ms Field power dissipation 3.22 W @ 28.8V DC DC field power Supply voltage - 24V DC nom Voltage range - 10…28.
DeviceNet Digital Base Terminal Block CompactBlock LDX I/O 1790D-TOW6 Attribute Value Relay type Form A, normally open Single pole, single throw Output delay time, off to on, max 10 ms Relay coil power dissipation 1.7 W @ 28.8V DC DC relay coil power Supply voltage - 24V DC nom Voltage range - 19.2…28.
DeviceNet Digital Base Terminal Block CompactBlock LDX I/O 23 1790D-T0A6 Attribute Value Number of outputs, nonisolated 6 Load voltage range 15…132V AC Load current, max 0.5 A rms Load current, min 10 mA rms Off-state Leakage current, max 1.0 mA rms @ 100V rms 60 Hz On-state voltage drop, max 1.
DeviceNet Digital Base Terminal Block CompactBlock LDX I/O General Attribute Value Network protocol Slave messaging: • Poll command • Bit Strobe command • Cyclic command • COS command Status indicators Module Status - red/green Network Status - red/green Number of nodes 64 max - rotary switch-type node address setting Communication rate 125 Kbps, 250 Kbps, 500 Kbps - auto baud rate selection Dimensions (HxWxD), approx. 16pt base blocks: 52 x 104 x 42 mm (2.03 x 4.07 x 1.64 in.
DeviceNet Digital Base Terminal Block CompactBlock LDX I/O 25 General Attribute Value Wiring category (1) 2 - on signal ports 2 - on communication ports Pilot duty rating Not Rated North American temperature code T5 (1) Use this conductor category information for planning conductor routing as described in Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1.
DeviceNet Digital Base Terminal Block CompactBlock LDX I/O Environmental Attribute Value ESD immunity IEC 61000-4-2: 8 kV air discharges Radiated RF immunity IEC 61000-4-3: 10V/m with 1 kHz sine-wave 80%AM from 80…1000 MHz 10V/m with 1 kHz sine-wave 80%AM from 1.
DeviceNet Digital Base Terminal Block CompactBlock LDX I/O 27 Certifications Certification (when Value product is marked)(1) c-UL-us UL Listed Industrial Control Equipment, certified for US and Canada. See UL File E150833. UL Listed for Class I, Division 2 Group A,B,C,D Hazardous Locations, certified for U.S. and Canada. See UL File E195620. CE European Union 2004/108/EC EMC Directive, compliant with: EN 61326-1; Meas./Control/Lab.
Rockwell Automation Support Rockwell Automation provides technical information on the Web to assist you in using its products. At http://support.rockwellautomation.com, you can find technical manuals, a knowledge base of FAQs, technical and application notes, sample code and links to software service packs, and a MySupport feature that you can customize to make the best use of these tools.