Installation Instructions DeviceNet Digital Base D-shell Block CompactBlock LDX I/O Catalog Numbers 1790D-16BV0, 1790D-8BV8V, 1790D-8BV8B, 1790D-0B16, 1790D-0V16, 1790D-0W6, Series B Topic Page Important User Information 2 Prevent Electrostatic Discharge 3 Environment and Enclosure 4 North American Hazardous Location Approval 5 Before You Begin 6 Install the Base Block 6 Set the Node Address 6 Mount the Base Block 7 Mount on a Panel 8 Mount on DIN Rail 9 Mount the Optional Expansion B
DeviceNet Digital Base D-shell Block CompactBlock LDX I/O Important User Information Solid state equipment has operational characteristics differing from those of electromechanical equipment. Safety Guidelines for the Application, Installation and Maintenance of Solid State Controls (publication SGI-1.1 available from your local Rockwell Automation sales office or online at http://literature.rockwellautomation.
DeviceNet Digital Base D-shell Block CompactBlock LDX I/O 3 Prevent Electrostatic Discharge ATTENTION This equipment is sensitive to electrostatic discharge, which can cause internal damage and affect normal operation. Follow these guidelines when you handle this equipment: • Touch a grounded object to discharge potential static. • Wear an approved grounding wriststrap. • Do not touch connectors or pins on component boards. • Do not touch circuit components inside the equipment.
DeviceNet Digital Base D-shell Block CompactBlock LDX I/O Environment and Enclosure ATTENTION This equipment is intended for use in a Pollution Degree 2 industrial environment, in overvoltage Category II applications (as defined in IEC publication 60664-1), at altitudes up to 2000 m (6562 ft) without derating. This equipment is considered Group 1, Class A industrial equipment according to IEC/CISPR Publication 11.
DeviceNet Digital Base D-shell Block CompactBlock LDX I/O 5 ATTENTION To comply with the CE Low Voltage Directive (LVD), all wiring connections to this equipment must be powered from a source compliant with safety extra- low voltage (SELV) or protected extra-low voltage (PELV). To comply with UL restrictions, all wiring connections to this equipment must be powered from a source compliant with the class 2 or limited voltage/current.
DeviceNet Digital Base D-shell Block CompactBlock LDX I/O Before You Begin Read this section about CompactBlock LDX I/O block requirements. Current functions of CompactBlock LDX I/O blocks require the current, modular electronic data sheet (EDS) file for RSNetWorx for DeviceNet software, version 3.0 or later. These files are available online at www.ab.com. EDS files for blocks with matching catalog numbers for both D-Shell and terminal block versions are the same.
DeviceNet Digital Base D-shell Block CompactBlock LDX I/O 7 Node Address Setting In this example, the node address setting is 11. NODE ADDRESS MOD NET STATUS MSD 44202 LSD You can also set the node address through RSNetWorx for DeviceNet software or a similar configuration tool. When you use software configuration for the node address, set the switches between 64 and 99. Mount the Base Block Mount the base block to a panel or DIN rail.
DeviceNet Digital Base D-shell Block CompactBlock LDX I/O Mount on a Panel For panel mounting, use these steps. Block Dimensions 95 mm (3.74 in.) 41 mm (1.6 in.) Expansion Cover 44153 1. Place the block against the panel where you want it mounted. 2. Gently pull and position the expansion cover to the left. 3. Place a center punch, nail, or similar device through the mounting holes in the block and make two marks on the panel at the lower-left and upper-right corners of the module. 4.
DeviceNet Digital Base D-shell Block CompactBlock LDX I/O 9 Mount on DIN Rail For DIN-rail mounting, use these steps. 1. Hook the top slot of the base block over the DIN rail. Locking Lever 44154 2. Pull down on the locking lever while pressing the base block against the rail. 3. Push up on the locking lever to secure the base block to the rail when the base block is flush against the rail.
DeviceNet Digital Base D-shell Block CompactBlock LDX I/O Horizontal or Vertical Mounting Right Side Up Right Side Up Right Side Up Horizontal Mounting Right Side Up Upside Down Vertical Mounting Right Side Up The longer expansion cable (1790-15CMCBL) provides for up to 7 cm (2.76 in.) of space in between blocks. 44155 Right Side Up • To mount horizontally (left to right), add the expansion block in an end-to-end configuration.
DeviceNet Digital Base D-shell Block CompactBlock LDX I/O 11 See the figures for wiring information.
DeviceNet Digital Base D-shell Block CompactBlock LDX I/O 1790D-8BV8B Input/Output Block Wiring Diagram COM0 I1 I3 I0 19 18 37 17 16 35 36 I6 I4 15 34 I7 I5 I2 13 14 33 12 31 32 11 30 O0 O2 O4 O6 COM2 O1 O3 O5 O7 9 10 28 29 8 27 7 26 5 6 24 25 3 4 22 23 1 2 20 21 COM1 COM1 COM1 COM1 COM1 COM3 COM3 COM3 COM3 COM1 COM1 COM1 COM1 COM3 COM3 COM3 COM3 COM3 44167 For sinking inputs, wire Com 1 to Field Power (+) 24V dc and Com 0 to Field Power (-) GND.
DeviceNet Digital Base D-shell Block CompactBlock LDX I/O 13 1790D-0V16 Output Block Wiring Diagram O7 O8 COM0 O1 O10 O12 O3 O14 O5 O6 COM2 O0 O9 O11 O2 O13 O4 O15 19 18 37 17 16 35 36 15 34 13 14 33 12 30 31 32 11 9 10 28 29 8 27 7 26 5 6 24 25 3 4 22 23 1 2 20 21 COM1 COM0 COM0 COM0 COM0 COM2 COM2 COM2 COM2 COM0 COM0 COM0 COM0 COM3 COM2 COM2 COM2 COM2 44169 For sinking outputs, wire Com 0 and Com 2 to Field Power (+) 24V dc, and Com 1 and Com 3 to Field Power (-) GND.
DeviceNet Digital Base D-shell Block CompactBlock LDX I/O WARNING If you connect or disconnect the DeviceNet cable with power applied to this module or any device on the network, an electrical arc can occur. This could cause an explosion in hazardous location installations. Be sure that power is removed or the area is nonhazardous before proceeding. 1.
DeviceNet Digital Base D-shell Block CompactBlock LDX I/O 15 Interpret the LED Indicators Read this section for information about how to interpret block LED indicators and related procedures. For a module status indicator that is flashing red, refer to the cable break procedure section. The base block has the following indicators: • Block status • Network status • I/O status Interpret the LED Indicators LED Indicator Probable Cause Recommended Action Solid Red Unrecoverable fault in base unit.
DeviceNet Digital Base D-shell Block CompactBlock LDX I/O Interpret the LED Indicators LED Indicator Probable Cause Recommended Action Solid Green The module is operating in a normal condition, and the module is online with connections in the established state. As a group 2 module, the module is allocated to a master. None. Flashing Green The module is online with no connections in the established state. Establish connections to other nodes. As a group 2 module, allocate the module to a master.
DeviceNet Digital Base D-shell Block CompactBlock LDX I/O 17 All digital-expansion inputs produce data of 0 if the expansion cable is removed. No status is in the default produced assembly. Attribute 101 in the identity object reports module faults. If no faults are present, an explicit message GET command returns 0. If the ribbon cable is disconnected, it returns 0x04, which is for module location change. The module LED indicator also flashes indicating a fault if an expansion is disconnected.
DeviceNet Digital Base D-shell Block CompactBlock LDX I/O 1790D-OW6 ac/dc Relay Output Block Attribute Value Relay Type Form A, normally open, single pole, single throw Output Voltage Range (load dependent) 5…24V dc @ 2.0 A resistive 30V ac @ 2.0 A resistive Output Current Rating (at rated power) 2.0 A @ 5…24V dc resistive 2.0 A @ 30V dc resistive Load, Min 100 µA, 100 mV dc per point On-state Voltage Drop, Max 0.5V @ 2.
DeviceNet Digital Base D-shell Block CompactBlock LDX I/O 19 1790D-8BV8V, 1790D-8BV8B dc Input/Output Combination Base Block Attribute Value On-state Current 8 mA max per channel @ 28.8V dc Off-state Voltage, Max 5V dc Input Impedance, Nom 4.8 kΩ Output Outputs per Module 8 points non-isolated, sinking - 1790D-8BV8V 8 points non-isolated, sourcing - 1790D-8BV8B On-state Voltage, Min 10V dc min On-state Voltage, Nom 24V dc On-state Voltage, Max 28.8V dc On-state Voltage Drop 0.
DeviceNet Digital Base D-shell Block CompactBlock LDX I/O 1790D-OV16 and 1790D-OB16 dc Output Base Block Attribute Value Off-state Leakage, Max 0.5 mA Output Signal Delay, Off to On 0.5 ms max Output Signal Delay, On to Off, Max 1.0 ms Output Current Rating 0.5 A max per output, 4.0 A max per common Field Power Dissipation 2.76 W @ 28.
DeviceNet Digital Base D-shell Block CompactBlock LDX I/O 21 Environmental Specifications Common To All Base Blocks in This Publication Attribute Value Radiated RF Immunity EC 61000-4-3: 10V/m with 1 kHz sine-wave 80%AM from 80…1000 MHz 10V/m with 1 kHz sine-wave 80%AM from 1.
DeviceNet Digital Base D-shell Block CompactBlock LDX I/O Environmental Specifications Common To All Base Blocks in This Publication Attribute Value Network Protocol Slave messaging: • Poll command • Bit Strobe command • Cyclic command • COS command LED Indicators 1 red/green module status, 1 red/green network status Number of Nodes 64 max - rotary switch-type node address setting Communication Rate 125 Kbps, 250 Kbps, 500 Kbps - auto baud rate selection (1) Use this Conductor Category informa
DeviceNet Digital Base D-shell Block CompactBlock LDX I/O 23 Certification Attribute Certification(1) (when product is marked) (1) Value c-UL-us UL Listed Industrial Control Equipment, certified for U.S. and Canada. See UL File E65584. c-UL-us UL Listed for Class I, Division 2, Group A,B,C,D Hazardous Locations, certified for U.S. and Canada. See UL File E194810. CE European Union 89/336/EEC EMC Directive, compliant with: EN 50082-2; Industrial Immunity EN 61326; Meas./Control/Lab.
Rockwell Automation Support Rockwell Automation provides technical information on the web to assist you in using its products. At http://support.rockwellautomation.com, you can find technical manuals, a knowledge base of FAQs, technical and application notes, sample code and links to software service packs, and a MySupport feature that you can customize to make the best use of these tools.