Installation Instructions DeviceNet Analog Base Terminal Block CompactBlock LDX I/O (Cat. Nos. 1790D-TN4C0, -TN0C2, -TN4V0, -TN0V2) What This Document Describes This document describes how to install your CompactBlock LDX™ I/O blocks.
Important User Information Because of the variety of uses for the products described in this publication, those responsible for the application and use of these products must satisfy themselves that all necessary steps have been taken to assure that each application and use meets all performance and safety requirements, including any applicable laws, regulations, codes and standards.
ATTENTION Identifies information about practices or circumstances that can lead to personal injury or death, property damage, or economic loss. ! IMPORTANT ATTENTION ! Identifies information that is critical for successful application and understanding of the product. Preventing Electrostatic Discharge This equipment is sensitive to electrostatic discharge, which can cause internal damage and affect normal operation.
ATTENTION ! Environment and Enclosure This equipment is intended for use in a Pollution Degree 2 industrial environment, in overvoltage Category II applications (as defined in IEC publication 60664-1), at altitudes up to 2000 meters without derating. This equipment is considered Group 1, Class A industrial equipment according to IEC/CISPR Publication 11.
Installing CompactBlock LDX I/O Follow these steps to install the block: 1. Set the node address on the base block. 2. Mount the base block. 3. Mount the optional expansion blocks. 4. Wire the terminal blocks. 5. Connect the DeviceNet cable. These steps are explained in detail in the following procedures. Set the Node Address on the Base Block Each base block comes with its internal program set for node address 63. To reset the node address, adjust the switches on the front of the block.
Mount the Base Block You can mount the base block to a panel or DIN rail. We recommend that you ground the panel or DIN rail before mounting the block. IMPORTANT The analog base module can accommodate a maximum of two discrete expansion modules. WARNING ! When used in a Class I, Division 2, hazardous location, this equipment must be mounted in a suitable enclosure with the proper wiring method that complies with the governing electrical codes. Panel Mounting 1.
5. Replace the block on the panel and place a screw through each of the two mounting holes. Tighten the screws until the block is firmly in place. 95 mm 3.74 in 41 mm 1.6 in k LDX CompactBloc 1790-16BVOX EXPANSION UNIT 16 INPUTS-DCPOW ER Expansion Cover 7 7 0 0 DIN Rail Mounting 1. Hook the top slot of the block over the DIN Rail. 2. Pull down on the locking lever while pressing the block against the rail. f Locking Lever 3.
Mount the Optional Expansion Blocks Mount the expansion block by connecting it to a previously-installed CompactBlock LDX I/O base or expansion block. Beginning with the base block, you can mount your expansion blocks either horizontally or vertically: • horizontally (left to right) - add expansion blocks in an end-to-end configuration • vertically (up or down) - add expansion blocks either up or down in a back-to-back configuration.
1790D-TN4CO Current Analog Input Module Terminal Block Wiring +24V CH1 CH0 1 3 5 2 6 NC NC NC 7 4 NC CH3 CH2 11 9 8 12 10 NC 17 15 13 18 16 14 19 20 GND COM1 COM3 NC NC COM0 COM2 NC NC NC • Wire pin 1 to Field Power (+) 24Vdc Wire pin 2 to Field Power (-) GND 1790D-TN0C2 Current Analog Input Module Terminal Block Wiring +24V CH1 CH0 1 3 2 NC NC NC 5 4 7 6 NC NC NC 11 9 8 12 10 NC 17 15 13 18 16 14 19 20 GND COM1 NC NC NC COM0 NC NC NC NC • Wire pin 1 to Field
Connect the DeviceNet Cable Follow these procedures when connecting the DeviceNet cable to the base block. The required DeviceNet connector is not supplied with the block; you must purchase it separately.
Once you have properly wired the drop line to the connector, attach the connector to the block. If applicable, use the locking screws on the connector to fasten it to the block.
1790D-TN0C2, -TN0V2 Output Data File Wor d Bit Position 0 Not Used Analog Output Data Channel 0 1 Not Used Analog Output Data Channel 1 1 5 1 4 1 3 1 2 1 1 1 0 9 8 7 6 5 4 3 2 1 Word/Bit Descriptions for 1790D-TN0C2, -TN0V2 Analog Output Module Word Decimal Bit Description Write Word 0 Bits 00-11 Channel 0 output data Bits 12-15 Not used: Set to 0 Write Word 1 Bits 00-11 Channel 1 output data Bits 12-15 Not used: Set to 0 Troubleshoot with the Indicators The 1790D I/O
I/O Channel LED Status Indicator 1790D-TN4V0 1790D-TN4C0 Status: Description: Status: Description: Flashing Green/ Red Power up Flashing Green/ Red Power up Off Off line Off Off line Red On line and no field power Red On line and no field power Red DeviceNet connection and no field power Red DeviceNet connection and no field power Green Field power and open wire Flashing Red1 Field power and open wire (4-20mA range only)2 Green Field power and valid input Green Field power a
I/O Channel LED Status Indicator 1790D-TN0V2 1790D-TN0C2 Status: Description: Status: Description: Flashing Green/ Red Power up Flashing Green/ Red Power up Off Off line Off Off line Off On line and no field power Off On line and no field power Green DeviceNet connection and no field power Green DeviceNet connection and no field power Green Field power and open wire Green Field power and open wire Green Field power and valid output Green Field power and valid output Flashin
Vibration 2g @ 10-500Hz IEC60068-2-6 (Test Fc, Operating) Shock Operating Non-operating 10g 30g IEC60068-2-27 (Test Ea, Unpackaged Shock) Emissions Group 1, Class A CISPR 11 ESD Immunity 8kV air discharges IEC 61000-4-2 Radiated RF Immunity 10V/m with 1kHz sine-wave 80%AM from 80MHz to 1000MHz 10V/m with 200Hz 50% Pulse 100%AM @ 900Mhz IEC 61000-4-3 EFT/B Immunity +1kV @ 5kHz on power ports +2kV @ 5kHz on signal ports +2kV @ 5kHz on communications ports IEC 61000-4-4 Surge Transient Immunity
DeviceNet Specifications Network protocol I/O Slave messaging: - Poll command - Bit Strobe command - Cyclic command - COS command Network length 500 meters maximum @ 125Kbps 100 meters maximum @ 500Kbps Indicators 1 red/green module status 1 red/green network status Number of nodes 64 maximum - rotary switch type node address setting Communication rate 125Kbps, 250Kbps, 500Kbps - auto baud rate selection Isolation Type test 1250Vac rms for 60 seconds between field power and DeviceNet (I/O to lo
4-Channel Analog Current Input Module Specifications 1790D-TN4C0 Inputs per module 4 channel single-ended, non-isolated Input Current (software configurable) 4-20mA (default) 0-20mA Resolution 12 bits-unipolar 1/4096 maximum 3.90µA/bit (4-20mA) 4.88µA/bit (0-20mA) Converted Data Binary data 0000 to 0fff (max scale) Conversion Time 10ms/channel Overall accuracy 0.
2 Channel Analog Current Output Module Specifications 1790D-TN0C2 Outputs per module 2 channel single-ended, non-isolated Output Current 0-20mA Resolution 12 bits 1/4096 maximum 4.88µA/bit Converted Data Binary data 0000 to 0fff (max scale) Conversion Time 2ms/channel Overall accuracy 0.
4 Channel Analog Voltage Input Module Specifications 1790D-TN4V0 Inputs per module 4 channel single-ended, non-isolated Input Voltage 0-10V Resolution 12 bits-unipolar 1/4096 maximum 2.44mV/bit Converted Data Binary data 0000 to 0fff (max scale) Conversion Time 10ms/channel Overall accuracy 0.
2 Channel Analog Voltage Output Module Specifications 1790D-TN0V2 Outputs per module 2 channel single-ended, non-isolated Output Voltage 0-10V Resolution 12 bits-unipolar 1/4096 maximum 2.44mV/bit Converted Data Binary data 0000 to 0fff (max scale) Conversion Time 2ms/channel Overall accuracy 0.2% Full scale @0°-55°C Calibration None required Allowable external output load resistance 1KΩ minimum Output Impedance 0.
IMPORTANT Input and output wiring must be in accordance with Class 1, Division 2 wiring methods and in accordance with the authority having jurisdiction.
The following information applies when operating this equipment in hazardous locations: Informations sur l’utilisation de cet équipement en environnements dangereux : Products marked “CL I, DIV 2, GP A, B, C, D” are suitable for use in Class I Division 2 Groups A, B, C, D, Hazardous Locations and nonhazardous locations only. Each product is supplied with markings on the rating nameplate indicating the hazardous location temperature code.
Publication 1790-IN002B-EN-P - April 2003
This product has been tested at an Open Device Vendors Association, Inc. (ODVA) authorized independent test laboratory and found to comply with ODVA Conformance Test. Please contact the ODVA website (http://www.odva.org) for listing of products tested by ODVA independent test labs for further details. CompactBlock LDX and RSNetWorx for DeviceNet are trademarks of Rockwell Automation. DeviceNet is a trademark of Open DeviceNet Vendor Association.