Installation Instructions DeviceNet 32 Point Digital Base Terminal Block CompactBlock LDX I/O Catalog Numbers 1790D-T16BV16V, 1790D-T16BV16B, 1790D-T0B32, 1790D-T32BVO, 1790D-T0V32 Series B Topic Page Important User Information 2 Preventing Electrostatic Discharge 3 Environment and Enclosure 4 North American Hazardous Location Approval 5 Before You Begin 5 Install the Base Block 6 Set the Node Address 6 Mount the Base Block 7 Mount the Optional Expansion Block 8 Wiring the Terminal Blo
DeviceNet 32 Point Digital Base Terminal Block CompactBlock LDX I/O Important User Information Solid state equipment has operational characteristics differing from those of electromechanical equipment. Safety Guidelines for the Application, Installation and Maintenance of Solid State Controls (publication SGI-1.1 available from your local Rockwell Automation sales office or online at http://literature.rockwellautomation.
DeviceNet 32 Point Digital Base Terminal Block CompactBlock LDX I/O 3 Preventing Electrostatic Discharge ATTENTION This equipment is sensitive to electrostatic discharge, which can cause internal damage and affect normal operation. Follow these guidelines when you handle this equipment: • Touch a grounded object to discharge potential static. • Wear an approved grounding wriststrap. • Do not touch connectors or pins on component boards. • Do not touch circuit components inside the equipment.
DeviceNet 32 Point Digital Base Terminal Block CompactBlock LDX I/O Environment and Enclosure ATTENTION This equipment is intended for use in a Pollution Degree 2 industrial environment, in overvoltage Category II applications (as defined in IEC publication 60664-1), at altitudes up to 2000 meters (6562 ft) without derating. This equipment is considered Group 1, Class A industrial equipment according to IEC/CISPR Publication 11.
DeviceNet 32 Point Digital Base Terminal Block CompactBlock LDX I/O 5 North American Hazardous Location Approval The following information applies when operating this equipment in hazardous locations: Informations sur l’utilisation de cet équipement en environnements dangereux: Products marked "CL I, DIV 2, GP A, B, C, D" are suitable for use in Class I Division 2 Groups A, B, C, D, Hazardous Locations and nonhazardous locations only.
DeviceNet 32 Point Digital Base Terminal Block CompactBlock LDX I/O of the blocks. For example, for the EDS file for 1790D-T16BV16B blocks, use the EDS file labelled 1790D-16BV16B. Install the Base Block To install the base block: • • • • • set the node address on the base block. mount the base block. mount the optional expansion blocks. wire the terminal block. connect the DeviceNet cable.
DeviceNet 32 Point Digital Base Terminal Block CompactBlock LDX I/O 7 Mount the Base Block Mount the base block to a panel or DIN rail. We recommend that you ground the panel or DIN rail before mounting the block. Dimensions 166 mm (6.53 in.) 1790D-T3 2BVO 42.5 mm (1.67 in.
DeviceNet 32 Point Digital Base Terminal Block CompactBlock LDX I/O Mount on DIN Rail For DIN-rail mounting, use these steps. 1. Hook the top slot of the base block over the DIN rail. 44253 Locking Lever 2. Pull down on the locking lever while pressing the base block against the rail. 3. Push up on the locking lever to secure the base block to the rail when the base block is flush against the rail. Mount the Optional Expansion Block To mount the optional expansion block, use these steps. 1.
DeviceNet 32 Point Digital Base Terminal Block CompactBlock LDX I/O 9 • To mount vertically (up or down), add an expansion block either up or down in a back-to-back configuration. In this configuration, you must use the optional 15 cm (5.9 in.) ribbon cable, catalog number 1790-15CMCBL, and alternately position the block in a right-side up, upside-down fashion. Right Side Up The longer expansion cable, catalog number 1790-15CMCBL, provides for up to 7 cm (2.76 in.) of space between blocks.
DeviceNet 32 Point Digital Base Terminal Block CompactBlock LDX I/O 1790D-T32BV0 Input Base Block Wiring Diagram COM 0 COM 0 IN0 IN1 IN2 IN3 IN4 IN5 IN6 IN7 IN8 IN9 IN10 IN11 IN12 IN14 COM 1 IN16 IN13 IN15 COM 1 IN18 IN17 IN19 IN20 IN21 IN22 IN23 IN24 IN25 IN26 IN27 IN28 IN29 IN30 IN31 44254 For inputs 0…15: For sinking inputs, wire COM 0 to Field Power (-) GND. For sourcing inputs, wire COM 0 to Field Power (+) 24V dc.
DeviceNet 32 Point Digital Base Terminal Block CompactBlock LDX I/O 11 1790D-T16BV16B Input/Output Base Block Wiring Diagram COM COM IN0 IN1 IN2 IN3 IN5 IN4 IN6 IN7 IN8 IN9 IN10 IN11 IN12 IN14 IN13 IN15 VDC OUT 0 OUT2 OUT4 OUT6 OUT8 OUT10 OUT12 OUT14 GND OUT1 OUT3 OUT5 OUT7 OUT9 OUT11 OUT13 OUT15 DC-IN TR-OUT 44256 For sinking inputs, wire COM to Field Power (-) GND. For sourcing inputs, wire COM to Field Power (+) 24V dc. Note that COM are internally connected.
DeviceNet 32 Point Digital Base Terminal Block CompactBlock LDX I/O 1790D-T0V32 Input/Output Base Block Wiring Diagram VDC0 OUT0 GND0 OUT2 OUT4 OUT6 OUT8 OUT10 OUT12 OUT14 24V OUT16 OUT18 OUT20 OUT22 OUT24 OUT26 OUT28 OUT30 OUT1 OUT3 OUT5 OUT7 OUT9 OUT11 OUT13 OUT15 GND0 OUT17 OUT19 OUT21 OUT23 OUT25 OUT27 OUT29 OUT31 44258 For sinking outputs, wire V dc 0 and V dc 1 to Field Power (+) 24V dc, and wire GND0 and GND1 to Field Power (-) GND.
DeviceNet 32 Point Digital Base Terminal Block CompactBlock LDX I/O 13 1. Connect the DeviceNet wiring (drop line) to one of the DeviceNet connectors as shown in the figure, noting that a color-coded wiring diagram is printed next to the connector on the left side of the base block.
DeviceNet 32 Point Digital Base Terminal Block CompactBlock LDX I/O Status Indicators Indicator Status Description Module Solid red Unrecoverable fault in base unit. Replace base block. Flashing red Fault in expansion unit, or Node address switches do not match current node address. Reconnect or replace, as needed. Solid green Normal operation. Off No power. Apply power to device. Solid red Module node number is a duplicate of an existing node, or network communication issues exist.
DeviceNet 32 Point Digital Base Terminal Block CompactBlock LDX I/O 15 I/O Status Indicators Indicator Status Description Each output None Output is not energized. Green Output is energized. None No valid input is present. Green Valid input is present.
DeviceNet 32 Point Digital Base Terminal Block CompactBlock LDX I/O Specifications Universal DC Input Base Block - 1790D-T32BV0 Attribute Value Number of inputs 32 Input type Sink, source 24V dc Voltage, off-state input, max 5V dc Voltage, on-state input, max 28.8V dc Voltage, on-state input, nom 24V dc Voltage, on-state input, min 9.6V dc Current, off-state input, max 1.5 mA @ 5V dc Current, on-state input, max 8 mA @ 28.8V dc per channel Input impedance, nom 4.
DeviceNet 32 Point Digital Base Terminal Block CompactBlock LDX I/O 17 1790D-TOV32, 1790D-TOB32 Attribute Value Output signal delay, off to on, max 0.5 ms Output signal delay, on to off, max 1.0 ms Output current rating, output, max 0.5 A Output current rating, common, max 4.0 A Field power dissipation 2.76 W @ 28.8V dc DC field power Supply voltage - 24V dc nom Voltage range - 10…28.
DeviceNet 32 Point Digital Base Terminal Block CompactBlock LDX I/O 1790D-T16BV16V, 1790D-T16BV16B Attribute Value Leakage, off-state, max 0.5 mA Output signal delay, off to on, max 0.5 ms Output signal delay, on to off, max 1.0 ms Field power dissipation 3.22 W @ 28.8V dc DC field power Supply voltage - 24V dc nom Voltage range - 10…28.8V dc General Attribute Value DeviceNet power Supply voltage - 24V dc nom Voltage range - 10…25V dc DeviceNet power dissipation 1.
DeviceNet 32 Point Digital Base Terminal Block CompactBlock LDX I/O 19 General Attribute Value Enclosure type rating Meets IP20 Isolation voltage 50V dc (continuous), Basic Insulation Type Type tested at 500V ac for 60 s, I/O to system No isolation between individual I/O channels Mounting DIN rail or panel Wiring, terminal block (M3.0) screw torque 0.9 Nm (8 lb-in) Wire size 0.25... 2.5 mm² (22...14 AWG) solid or stranded copper wire rated at 75 °C (167 °F ) or greater 1.2 mm (3/64 in.
DeviceNet 32 Point Digital Base Terminal Block CompactBlock LDX I/O Environmental Attribute Value Temperature, operating IEC 60068-2-1 (Test Ad, Operating Cold), IEC 60068-2-2 (Test Bd, Operating Dry Heat), IEC 60068-2-14 (Test Nb, Operating Thermal Shock): 0…60 °C (32…140 °F) Temperature, storage IEC 60068-2-1 (Test Ab, Unpackaged Non-operating Cold), IEC 60068-2-2 (Test Bb, Unpackaged Non-operating Dry Heat), IEC 60068-2-14 (Test Na, Unpackaged Non-operating Thermal Shock): -40…85 °C (-40…185 °F)
DeviceNet 32 Point Digital Base Terminal Block CompactBlock LDX I/O 21 Environmental Attribute Value EFT/B immunity IEC 61000-4-4: ±2 kV at 5 kHz on signal ports ±2 kV at 5 kHz on communications ports Surge transient immunity IEC 61000-4-5: ±1.
DeviceNet 32 Point Digital Base Terminal Block CompactBlock LDX I/O Notes: Publication 1790-IN014A-EN-P - March 2008
DeviceNet 32 Point Digital Base Terminal Block CompactBlock LDX I/O 23 Notes: Publication 1790-IN014A-EN-P - March 2008
Rockwell Automation Support Rockwell Automation provides technical information on the Web to assist you in using its products. At http://support.rockwellautomation.com, you can find technical manuals, a knowledge base of FAQs, technical and application notes, sample code and links to software service packs, and a MySupport feature that you can customize to make the best use of these tools.