B-24 PROFIBUS Modules Installation, Wiring, Module Data, Status and Channel Configuration
PROFIBUS DP
Specifications
Table B.7 lists the module specifications.
Table B.7
PROFIBUS DP Specifications
Network Protocol PROFIBUSDP (EN50170)
Redundancy Not supported
Repeater Control Signal RS-485 signal
Implementation Type DPC31
Freeze Mode Supported
Sync Mode Supported
Auto Baud Rate Supported
Fail Safe Mode Supported
Station Type Slave
FMS Support Not supported
Indicators 1 red/green - module status
1 red/green - network status
Number of Nodes 100 maximum - roatary switch type node address
setting (0-99)
Network Length/Communication Rate 9.6Kbps @ 1000m (3280ft)
19.2Kbps @ 1000m (3280ft)
45.45Kbps @ 1000m (3280ft)
93.75Kbps @ 1000m (3280ft)
187.5Kbps @ 1000m (3280ft)
500Kbps @ 400m (1312ft)
1.5mbps @ 200m (656ft)
3mbps @ 100m (328ft)
6mbps @ 100m (328ft)
12mbps @ 100m (328ft)
Isolation Type test 1250Vac rms for 60 seconds between
field power and PROFIBUS (I/O to logic)
PROFIBUS Power Supply voltage - 24V dc nominal
Voltage range - 19.2-28.8V dc
Power dissipation - 2W maximum @ 28.8V dc
Field Power Supply voltage - 24V dc nominal
Voltage range - 21.6-26.4V dc
Power dissipation - 1.5W maximum @ 26.4V dc