User Manual

Publication 1790-UM001A-EN-P - March 2002
4-2 Module Data, Status, and Channel Configuration for Analog Output Modules
Analog Output Data File
The structure of the output data file is shown below.
1790D-N0C2/-TN0C2, 1790D-N0V2/-TN0V2 Output Data File
Word/Bit Descriptions
Word Bit Position
1514131211109876543210
0 Not Used Analog Output Data Channel 0
1 Not Used Analog Output Data Channel 1
Word Decimal Bit Description
Write Word 0 Bits 00-11 Channel 0 output data
Bits 12-15 Not used: Set to 0
Write Word 1 Bits 00-11 Channel 1 output data
Bits 12-15 Not used: Set to 0