4-Channel Input RTD Base Block Specifications
1790P-T4R0
Inputs per module 4 channel, RTD/Resistance Input
Input Range 1-625
Sensors Supported Sensor Type Degree Counts Resolution
Resistance 100m
Ω 1 to 625Ω 10 to 6250 100mΩ
Resistance 10mΩ 1 to 327Ω 100 to
32700
10mΩ
100ohm Pt/α =0.00385 -200 to
+850°C
-2000 to
+8500
0.1°C
200ohm Pt/
α =0.00385 -200 to
+850°C
-2000 to
+8500
0.1°C
500ohm Pt/α =0.00385 -200 to
+650°C
-2000 to
+6500
0.1°C
100ohm Pt/
α =0.003916 -200 to
+640°C
-2000 to
+6400
0.1°C
200ohm Pt/α =0.003916 -200 to
+640°C
-2000 to
+6400
0.1°C
500ohm Pt/
α =0.003916 -200 to
+640°C
-2000 to
+6400
0.1°C
100ohm Nickel -60 to
250°C
-600 to
2500
0.1°C
120ohm Nickel -80 to
260°C
-800 to
2600
0.1°C
200ohm Nickel -60 to
250°C
-600 to
2500
0.1°C
500ohm Nickel -60 to
250°C
-600 to
2500
0.1°C
Resolution 16 bits across 625ohms, 0.1°C/bit or 0.1°F/bit (RTD Sensors)
20bit Sigma-Delta modulation converter
Data Format 16 bit Integer (2’s compliment)
Module Scan Time 8ms/channel @ Notch Filter = 60Hz
Overall accuracy 0.2% Full scale @0°C-60°C
Settable Notch Filter 10Hz (default), 25Hz, 50Hz, 60Hz, 100Hz, 250Hz, 500Hz
Open Wire Detection Out of range, open wiring
Excitation Current 1mA
Input Impedance 5M ohm