Installation Instructions Instruction Manual

FOUNDATION Fieldbus Junction Box 11
Rockwell Automation Publication 1788-IN006A-EN-P - September 2014
Set DIP Switches
Use the DIP switches on the front of the junction box to enable or disable the
built-in bus terminator and to configure the auto-reset function.
1788-FBJB4R
1788-FBJB6
Switch Setting
1 Enable the bus terminator
2 Not used
3 Auto-reset in one hour
4 Auto-balance in ring topology
Switch Setting
1Enable the bus terminator
2 Not used
3 & 4 Auto-reset as follows:
43 Mode
00 No reset
01 Auto-reset in 5 min
1 0 Auto-reset in 1 hour
1 1 Auto reset in 12 hours