Installation Instructions

10 ControlNet Daughtercards
Publication 1788-IN005B-EN-P - October 2005
To wire the module:
1. Hold down the latch and insert the Channel A zipcord connector into the duplex
socket until the pins and latch lock into place.
2. Make sure you insert the blue pin (receive) of the zipcord connector into the left Rx
and the black pin (transmit) into the right Tx socket.
ControlNet Network Topology Example
If Your Network Supports Connect the Fiber Cable
nonredundant media
(1788-CNF or -CNFR)
to the channel A connector on the module
(channel B on the 1788-CNFR is not used.)
(1)
(1)
Recommended when using channel A for non-redundant media.
redundant media
(1788-CNFR)
from trunk-cable A to channel A on the 1788-CNFR and from trunk-cable B
to channel B on the 1788-CNFR.
IMPORTANT
It is not necessary to install nodes on coax segments. If you are only
using the repeaters to extend, then install a 75-ohm terminator
(1786-XT) on the BNC coax connector on the fiber repeater adapter
(1786-RPA). Do this to all repeaters that are not connected to coax
segments.