User Manual Owner manual

1788-6.5.1 - January 1999
Chapter
4
Using the ControlNet-to-FOUNDATION
Fieldbus H1 Linking Device
This chapter describes:
the blocks in the linking device
configuring the linking device to access the AI, AO, DI, DO function
blocks on the Fieldbus network from ControlNet
attributes of the created ControlNet objects, assembly objects, alarm
handling
ControlNet connection details
Blocks in the Linking Device
The linking device is similar to an I/O subsystem. An I/O subsystem
typically contains several I/O modules. Each module has a number of
channels. The channels perform either analog input, analog output, discrete
input, or discrete output functions. The linking device models the I/O
modules in software. The linking device has four types of function blocks:
Multiple Analog Input (MAI)
Multiple Analog Output (MAO)
Multiple Discrete Input (MDI)
Multiple Discrete Output (MDO)
Each of these function blocks has eight channels. Each channel is a
combination of a value and Fieldbus status.
You can connect an analog input function block on the Fieldbus network to
a channel on the MAI block, just as you would wire a 4-20ma analog input
to an analog channel in your I/O subsystem. The main difference is that the
Fieldbus function blocks do considerable processing. The channel value
represents a scaled value in engineering units. Each value has an associated
status. The status is more than a boolean of good or bad. It has four major
status values of Good or Bad, with 16 sub-status values for each major
status, and four limits.