Installation Instructions

Publication 1787-5.8 - February 1999 PN 955138-62
Supersedes Publication xxxxxxx-xx - xxxxxxx-xx Copyright 1998 of Rockwell International Corporation. Printed in the U.S.A.
Table 1: Specifications
DeviceNet is a trademark of Open Device Vendor Association (ODVA).
Power
Connector
3-pin IEC Line Frequency 48-62 Hz
Fuse Class 2 type accepted
1
Turn-on Time
(with full load)
250msec max 95% of final
value
Size 5” x 6.5” x 11” Isolation output isolated from AC and
chassis ground
DC Connector Phoenix Combicon style 5-pin 5.08mm pitch
female and mating connector
Operating Temperature 0 - 60
°
C min 0 - 75
°
C with
30% derating at 75
°
C
32 - 140
°
F min 32 - 167
°
F
with 30% derating at 167
°
F
DC Connector
Pins
Pin 1, 24V+; Pin 3, Chassis ground; Pin 5,
24V-
Storage
Temperature
-40 - 85
°
C
-40- 185
°
F
Indicators LED power good indicator Humidity 95% non-condensing
Mounting Flange Electrostatic Discharge 4KV contact 8KV air
Enclosure Vented enclosure (indoor use) Vibration 2g, 10-500hz
Input Voltage 115V±10%
230V±10% selectable
Shock 30g, 11ms half cycle
Output Voltage 24V dc ± 1% Surge 4KV common mode,
2KV differential mode
Output Current Nameplate rating of 100VA to be consistent
with NEC Class 2
Peak output currents 5.25 A
Electrical Fast Transient 2KV
Ripple 250mV Radiated Immunity 10V/M 80 MHZ- 1GHZ
Load
Capacitance
Capability
7000uF load Agency Certification (when
product or packaging is
marked)
1
Contact the manufacturer for information on replacing fuses for your power supply.
marked for all applicable directives
1310 class 2 power limited circuits
223 - M91 with T.I.L. No. CA 2A.