User manual

Installing Your 1785-BEM Module
Chapter 4
4-19
Figure 4.13
Channel
2B Connections Added Between a PLC-5
and a 1785-BEM Module
1771 –P4S
Power Supply
1771 –P4S
Power Supply
1785 –BCM Module
Local I/O ChassisLocal I/O Chassis
1785 –BEM Module
1785 –BCM Module
1785 –BEM Module
19094
See Note
Shield
See Note
Shield
See Note
See Note
Data Highway Plus connect the signal conductors with Clear, Shield, and Blue insulation to
terminals 1, SH, and 2 of PLC 5/40 or 5/60 processor respectively, as well as to terminals 18, 19, and 20 of
1785 –BEM module.
Remote I/O connect the signal conductors with Blue, Shield, and Clear insulation to terminals 1, SH, and 2 of
PLC –5/40 or 5/60 processor respectively, as well as to terminals 18, 19, and 20 of 1785 BEM module.
18
19
20
Wire channel for either Data Highway Plus or Remote I/O.
PLC-5/40, -5/60, -5/80
PLC-5/40, -5/60, -5/80
2. Connect the other end of the 1770-CD cable to terminals 18, 19, and
20 on the wiring arm of the 1785-BEM module in the same chassis as
shown in Figure 4.13.
3. Perform steps 1 and 2 for the other PLC-5/40, -5/60, or -5/80
processor and 1785-BEM module.