User manual

Assigning Addressing Modes,
Racks, and Groups
Chapter 4
4-16
Placing Complementary I/O Modules
See Table 4.B for a summary of 8-, 16-, and 32-point I/O module
placement guidelines. See Table 4.C for a summary of block-transfer
module placement guidelines.
Table 4.B
Placement
Summary for 8, 16, and 32point Modules Used in
Complementary I/O
Addressing
Method
Guidelines
Types of Modules Used: Placement
2Slot 8 point
Install input modules opposite output modules and output modules
opposite input modules
1Slot 8 point, 16point,
opposite input modules.
1/2Slot 8 point, 16point, 32point
Table 4.C
Placement
Summary for Blocktransfer Modules Used in
Complementary I/O
Addressing
Method
BlockTransfer Placement Guidelines in Primary Chassis
Using singleslot modules: Using doubleslot modules:
2Slot
The right slot of the primary I/O group can be
another singleslot block transfer module, or an
8point input or output module.
The left slot of the complementary I/O group must be
empty.
In the right slot of the complementary I/O group, you
can place an 8point output module; this slot must be
empty if the corresponding slot in the primary I/O
group is a singleslot block transfer module.
The left slot of the complementary I/O group must be
empty.
In the right slot of the complementary I/O group, you
can only place an 8point output module (if any).
1Slot Leave the corresponding I/O group in the
complementary chassis empty.
The left slot of the two corresponding I/O slots in the
complementary chassis must be empty.
In the right slot of the two corresponding I/O slots in
the complementary chassis, you can place an input,
output, or singleslot block transfer module (if any);
the modules can be either 8point or 16point I/O
modules.
1/2Slot Leave the corresponding I/O group in the
complementary chassis empty.
The left slot of the two corresponding I/O slots in the
complementary chassis must be empty.
In the right slot of the two corresponding I/O slots in
the complementary chassis, you can place an input,
output, or singleslot block transfer module (if any);
the modules can be 8point ,16point and/or 32point
I/O modules.