User manual
Assigning Addressing Modes,
Racks, and Groups
Chapter 4
4-7
32-Point I/O Modules
To use 32-point I/O modules with 1-slot addressing, you must install, as a
pair, an input module and an output module in two adjacent slots (even/odd
pair) of the I/O chassis, beginning with I/O slot 0. If you cannot pair the
modules in this way, one of the two slots of the pair must be empty. For
example, if I/O slot 0 holds a 32-point input module, I/O slot 1 must hold
an 8-, 16-, or 32-point output module (or a module using the backplane for
power only); otherwise the slot must be empty.
IOI IOIOO
2301
0
1
2
3
4
5
6
7
0
1
2
3
4
5
6
7
4567
Word #
Word #
Output Image Table
Input Image Table
I/O Group Designation
Input/Output Designation
I/O Chassis with 1Slot Addressing
Slot 0
Input Module
I/O Group 0, 1
Slot 1
Output Module
I/O Group 0, 1
000
000
001
001
Output ImageTable Words Corresponding to I/O Groups 0 and 1.
Input
ImageT
able W
ords
Corresponding to I/O Groups 0 and 1.
17 16 15 14 12
10
07
06
05 03
02 01
00
04
11
13
17 16 15 14 12
10
07
06
05 03
02 01 00
04
11
13
17 16 15 14 12
10
07
06
05 03
02 01 00
04
11
13
17 16 15 14 12
10
07
06
05 03
02 01 00
04
11
13
1Slot
I/O Group with 32pt I/O Modules
14258