User manual

Placing System Hardware
Chapter 3
3-2
To allow for proper convection cooling in enclosures containing a
processor-resident chassis and remote I/O chassis, follow these guidelines.
Area reserved for disconnect.
transformer, control relays, motor
starters or other user devices.
13081
Minimum spacing requirements for a
processorresident chassis:
Mount the I/O chassis horizontally.
Allow 153 mm (6 in) above and below the chassis.
Allow 102 mm (4 in) on the sides of each chassis.
Allow 51 mm (2 in) vertically and horizontally between
any chassis and the wiring duct or terminal strips.
Leave any excess space at the top of the enclosure,
where the temperature is the highest.
102mm
(4")
153mm
(6")
51mm
(2")
102mm
(4")
Wiring Duct
153mm
(6")
51mm(2")