User manual

Addressing
Data Table Files 2-3
Data Table Files - Classic Processors
File Description
Number
(Default
File)
Maximum Size of File
(16-bit words and
structures)
Memory Used
PLC-5/10,
-5/12, -5/15
PLC-5/25
Output Image O 0 32 64 2/file + 1/word
Input Image I 1 32 64 2/file + 1/word
Status S 2 32 32 2/file + 1/word
Bit (binary) B 3-999 (3) 1000 words 2/file + 1/word
Timer T 3-999 (4) 3000 words/1000 structures 2/file + 3/structure
Counter C 3-999 (5) 3000 words/1000 structures 2/file + 3/structure
Control R 3-999 (6) 3000 words/1000 structures 2/file + 3/structure
Integer N 3-999 (7) 1000 words 2/file + 1/word
Floating Point F 3-999 (8) 1000 words 2/file + 2/structure
ASCII A 3 - 999 1000 words 2/file + 1/2 per
character
BCD D 3 - 999 1000 words 2/file + 1/word
Extra Storage 3 - 999
PLC-5 Memory
Data Table
program