User manual

Troubleshooting
Extended Local I/O 5-44
65530 0xFFFA MODULE DECLARED INVALID LENGTH A communication error between the adapter and
the module caused the transfer to be aborted.
Make sure that the module is properly seated in
the correct slot of the target node.
Make sure that the adapter’s power supply is
providing the proper voltage.
The target slot contains the wrong module type. Insert the proper module in the correct slot of the
target node.
An incorrect module or slot was entered in the
map table.
Edit the I/O map table to show the correct module
type and slot.
65531 0xFFFB INVALID READ DATA A communication error between the adapter and
the module caused the transfer to be aborted.
Make sure that the module is properly seated in
the correct slot of the target node.
Make sure that the adapter’s power supply is
providing the proper voltage.
The target slot contains the wrong module type. Insert the proper module in the correct slot of the
target node.
An incorrect module or slot was entered in the
map table.
Edit the I/O map table to show the correct module
type and slot.
65532 0xFFFC INVALID WRITE DATA A communication error between the adapter and
the module caused the transfer to be aborted.
Make sure that the module is properly seated in
the correct slot of the target node.
Make sure that the adapter’s power supply is
providing the proper voltage.
The target slot contains the wrong module type. Insert the proper module in the correct slot of the
target node.
An incorrect module or slot was entered in the
map table.
Edit the I/O map table to show the correct module
type and slot.
65533 0xFFFD DATA TABLE TOO SMALL The processor data table is too small to hold the
data to be transferred.
Increase the size of the data table to
accommodate the transfer length.
Decimal Code Hex. Code Error Message Explanation/Possible Cause(s) Possible Corrective Action(s)
ControlNet Errors