User manual

Troubleshooting
Extended Local I/O 5-43
Troubleshooting
Extended Local I/O 5-43
65527 0xFFF7 MODULE TIMED OUT The target slot is empty. Insert the proper module in the correct slot of the
target node.
The target slot contains the wrong module type.
An incorrect module or slot was entered in the
map table.
Edit the I/O map table to show the correct module
type and slot.
65529 0xFFF9 COMMUNICATION ERROR CAUSED LOSS
OF DATA
A communication error between the adapter and
the module caused the transfer to be aborted.
Make sure that the module is properly seated in
the correct slot of the target node.
Make sure that the adapter’s power supply is
providing the proper voltage.
The target slot contains the wrong module type. Insert the proper module in the correct slot of the
target node.
An incorrect module or slot was entered in the I/O
map table.
Edit the I/O map table to show the correct module
type and slot.
Decimal Code Hex. Code Error Message Explanation/Possible Cause(s) Possible Corrective Action(s)
ControlNet Errors